Technical Specifications
F-2
AC30V series Variable Speed Drive
ENVIRONMENTAL DETAILS
Operating Temperature
NORMAL DUTY
HEAVY DUTY
Operating temperature is defined as the surrounding air temperature of the drive, when the drive and other equipment adjacent
to it is operating at worst case conditions.
0
C to 40
C, derate up to a maximum of 50
C
0
C to 45
C, derate up to a maximum of 50
C
Output power is derated linearly at 2% per degree centigrade for temperature exceeding the maximum rating for the drive.
Storage Temperature
-25
C to +55
C
Shipping Temperature
-25
C to +70
C
Product Enclosure Rating
IP20 – remainder of surfaces (Europe)
UL (c-UL) Open Type (North America/Canada)
Cubicle Mounted
IP20
UL (c-UL) Open Type (North America/Canada)
Through-panel Mounted
IP20
UL (c-UL) Open Type (North America/Canada)
Altitude
If greater than 1000m above sea level, derate by 1% per 100m to a maximum of 2000m
Humidity
Maximum 85% relative humidity at 40
C non-condensing
Atmosphere
Non flammable, non corrosive and dust free
Climatic Conditions
Class 3k3, as defined by EN60721-3-3
Chemically Active Substances
For the standard product (which inherently includes our optimal level of conformal coating) compliance with EN60721-3-3 is as
follows –
a) Both classes 3C3 and 3C4 for hydrogen sulphide gas (H
2
S) at a gas concentration of 25ppm for 1200 hours.
b) Both classes 3C1 (rural) and 3C2 (urban) for all nine defined substances as defined in table 4.
Classes 3C1 and 3C2 are valid for both storage and transportation purposes.
Note - Product was tested and validated with a hydrogen sulphide environment of 25ppm for a continuous period of 1200 hours
and validated throughout the test period without failure.
Vibration
Test Fc of EN60068-2-6
10Hz<=f<=57Hz sinusoidal 0.075mm amplitude
57Hz<=f<=150Hz sinusoidal 1g
10 sweep cycles per axis on each of three mutually perpendicular axis
Safety
Overvoltage Category Overvoltage Category III (numeral defining an impulse withstand level)
Pollution Degree Pollution Degree II (non-conductive pollution, except for temporary condensation) for control electronics
Pollution Degree III (dirty air rating) for through-panel mounted parts
North America/Canada
Complies with the requirements of UL508C as an open-type drive.