Parameter Reference
D-46
AC30V series Variable Speed Drive
General Purpose IO
Monitor::Inputs and Outputs
Parameters::Option IO::General Purpose IO
The General Purpose IO parameters configure the use of the three IO Options, (
Error! Bookmark not defined.
). This group of parameters is
only visible when an IO Option is selected.
PNO Parameter Descriptions
Anin 11 Value, (Terminal X21.2)
The input value expressed as a percentage of range, (+/- 100%), following Offset and Scale.
Anin 12 Value, (Terminal X21.3)
The input value expressed as a percentage of range, (+/- 100%), following Offset and Scale.
Anin 13 Value, (Terminal X21.4)
The input value expressed as a percentage of range, (+/- 100%), following Offset and Scale.
Anin 11 Offset
The offset is expressed as a percentage of the hardware range. For example an offset of 10% is equivalent to 1V on the input.
The offset is added to the measured value.
Anin 11 Scale
The scale is a simple multiplication factor. The input voltage is converted to a percentage value.
1461 Anin 11 Offset
is added and
the result is multiplied by Scale. The result is presented in parameter
1181 Anin 11 Value
.
Anin 12 Offset
The offset is expressed as a percentage of the hardware range. For example an offset of 10% is equivalent to 1V on the input.
The offset is added to the measured value.
Anin 12 Scale
The scale is a simple multiplication factor. The input voltage is converted to a percentage value.
1463 Anin 12 Offset
is added and
the result is multiplied by Scale. The result is presented in parameter
1182 Anin 12 Value
.
Anin 13 Offset
The offset is expressed as a percentage of the hardware range. For example an offset of 10% is equivalent to 1V on the input.
The offset is added to the measured value.
Anin 13 Scale
The scale is a simple multiplication factor. The input voltage is converted to a percentage value.
1465 Anin 13 Offset
is added and
the result is multiplied by Scale. The result is presented in parameter
1183 Anin 13 Value
.