D-57
Parameter Reference
AC30V series Variable Speed Drive
PNO Parameter Descriptions
Anin 01 Value
Terminal X11.1
The value returned by the signal processing electronics. For unipolar ranges, (all except -10..10V), the value is expressed as a
percentage of the hardware range. For the -10..10V range the full range signal is expressed as -100% to +100%.
Anin 01 Break
When the input range is set to 4..20mA a break is defined as an input signal less than 3mA. Otherwise this parameter is set to
FALSE.
Anin 02 Value
Terminal X11.2
The value returned by the signal processing electronics. For the 0..10V range the value is expressed as a percentage of the
hardware range, (0 to 100%). For the -10..10V range the full range signal is expressed as -100% to +100%.
Anout 01 Value
Terminal X11.3
The desired output value expressed as a percentage of the output range.
Range
Mapping
0..10V
0% gives 0V, 100% gives 10V
0..20MA
0% gives 0mA, 100% gives 20mA
4..20MA
0% gives 4mA, 100% gives 20mA
Anout 02 Value
Terminal X11.4
The desired output value expressed as a percentage of the output range.
Range
Mapping
-10..10V
-100% gives -10V, 100% gives 10V
0..10V
0% gives 0V, 100% gives 10V