13-4
Fire Mode
AC30V series Variable Speed Drive
TRIPS AND AUTO RESTART
The following table summarizes which trips are disabled in the two modes of operation. Also shown are those trips which are designed to protect
the drive.
Caution
Disabling the Drive Protection trips will invalidate the drive’s warranty.
Selecting PARTIAL mode leaves the drive protection features enabled. Selecting FULL mode disables some of the drive protection features.
Caution
Regardless of the setting of
Level
, activating Fire Mode may cause damage to the motor or attached equipment.
ID Trip Name
Disabled in Partial mode Disabled in Full mode Drive Protection
1 OVER VOLTAGE
2 UNDER VOLTAGE
(1)
Note 1
Note 1
3 OVER CURRENT
4 STACK FAULT
5 STACK OVER CURRENT
6 CURRENT LIMIT
7 MOTOR STALL
8 INVERSE TIME
9 MOTOR I2T
10 LOW SPEED I
11 HEATSINK OVERTEMP
12 AMBIENT OVERTEMP
13 MOTOR OVERTEMP
14 EXTERNAL TRIP
15 BRAKE SHORT CCT
16 BRAKE RESISTOR
17 BRAKE SWITCH
18 LOCAL CONTROL
19 COMMS BREAK
20 LINE CONTACTOR
21 PHASE FAIL
22 VDC RIPPLE
23 BASE MODBUS BREAK
24 24V OVERLOAD
25 PMAC SPEED ERROR
26 OVERSPEED
27 SAFE TORQUE OFF
Note 1. The Under Voltage trip is enabled when Fire Mode is active, but the trip level is reduced by 50%.