Parameter Reference
D-134
AC30V series Variable Speed Drive
PNO
Name
Path(s)
Type
Default
Range
Units WQ
View
Notes MBus
0435 VHz User Volts
Parameters::Motor Control::Fluxing VHz
ARRAY[0..10]
STOPPED
ENGINEER
01397
0436 VHz User Volts[0]
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 100.0
%
STOPPED
ENGINEER
01399
0437 VHz User Volts[1]
Parameters::Motor Control::Fluxing VHz
REAL
10.0
0.0 to 100.0
%
STOPPED
ENGINEER
01401
0438 VHz User Volts[2]
Parameters::Motor Control::Fluxing VHz
REAL
20.0
0.0 to 100.0
%
STOPPED
ENGINEER
01403
0439 VHz User Volts[3]
Parameters::Motor Control::Fluxing VHz
REAL
30.0
0.0 to 100.0
%
STOPPED
ENGINEER
01405
0440 VHz User Volts[4]
Parameters::Motor Control::Fluxing VHz
REAL
40.0
0.0 to 100.0
%
STOPPED
ENGINEER
01407
0441 VHz User Volts[5]
Parameters::Motor Control::Fluxing VHz
REAL
50.0
0.0 to 100.0
%
STOPPED
ENGINEER
01409
0442 VHz User Volts[6]
Parameters::Motor Control::Fluxing VHz
REAL
60.0
0.0 to 100.0
%
STOPPED
ENGINEER
01411
0443 VHz User Volts[7]
Parameters::Motor Control::Fluxing VHz
REAL
70.0
0.0 to 100.0
%
STOPPED
ENGINEER
01413
0444 VHz User Volts[8]
Parameters::Motor Control::Fluxing VHz
REAL
80.0
0.0 to 100.0
%
STOPPED
ENGINEER
01415
0445 VHz User Volts[9]
Parameters::Motor Control::Fluxing VHz
REAL
90.0
0.0 to 100.0
%
STOPPED
ENGINEER
01417
0446 VHz User Volts[10]
Parameters::Motor Control::Fluxing VHz
REAL
100.0
0.0 to 100.0
%
STOPPED
ENGINEER
01419
0447 Fixed Boost
Same as PNO 422
REAL
0.0
0.0 to 25.0
%
ALWAYS
TECHNICIAN
6
01421
0448 Auto Boost
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 25.0
%
ALWAYS
TECHNICIAN
6
01423
0450 Acceleration Boost
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 25.0
%
ALWAYS
TECHNICIAN
01427
0451 Energy Saving Enable
Parameters::Motor Control::Fluxing VHz
BOOL
FALSE
ALWAYS
TECHNICIAN
01429
0455 Rated Motor Current
Setup::Motor Control::Motor Nameplate
Parameters::Motor Control::Motor Nameplate
REAL
1.00
0.00 to 10000.00
A
STOPPED
TECHNICIAN
6
01437
0456 Base Voltage
Same as PNO 455
REAL
400.00
0.00 to 1000.00
V
STOPPED
TECHNICIAN
6
01439
0457 Base Frequency
Same as PNO 455
REAL
50.00
0.00 to 1000.00
Hz
STOPPED
TECHNICIAN
6
01441
0458 Motor Poles
Same as PNO 455
INT
4,
2 to 1000
STOPPED
TECHNICIAN
6
01443
0459 Nameplate Speed
Same as PNO 455
REAL
1420.00
0.00 to 100000.00
RPM STOPPED
TECHNICIAN
6
01445
0460 Motor Power
Same as PNO 455
REAL
2.20
0.00 to 3000.00
kW
STOPPED
TECHNICIAN
6
01447
0461 Power Factor
Same as PNO 455
REAL
0.79
0.00 to 1.00
STOPPED
TECHNICIAN
6
01449
0464 100% Speed in RPM
Setup::Motor Control::Control and Type
Parameters::Motor Control::Scale Setpoint
REAL
1500.0
0.0 to 100000.0
RPM ALWAYS
TECHNICIAN
01455
0467 PMAC SVC Auto Values
Parameters::Motor Control::PMAC SVC
BOOL
TRUE
ALWAYS
TECHNICIAN
6
01461
0468 PMAC SVC LPF Speed Hz
Parameters::Motor Control::PMAC SVC
REAL
60.00
0.00 to 10000.00
Hz
ALWAYS
TECHNICIAN
6
01463
0469 PMAC SVC P Gain
Parameters::Motor Control::PMAC SVC
REAL
1.00
0.00 to 10000.00
ALWAYS
TECHNICIAN
6
01465
0470 PMAC SVC I Gain Hz
Parameters::Motor Control::PMAC SVC
REAL
20.00
0.00 to 10000.00
Hz
ALWAYS
TECHNICIAN
6
01467
0476 PMAC SVC Open Loop Strt
Parameters::Motor Control::PMAC SVC
BOOL
TRUE
ALWAYS
TECHNICIAN
01479
0477 PMAC SVC Start Time
Parameters::Motor Control::PMAC SVC
TIME
0.500
0.000 to 1000.000
s
ALWAYS
TECHNICIAN
01481
0478 PMAC SVC Start Cur
Setup::Motor Control::SVC PMAC
Parameters::Motor Control::PMAC SVC
REAL
10.0
0.0 to 200.0
%
ALWAYS
TECHNICIAN
01483
0479 PMAC SVC Start Speed
Same as PNO 478
REAL
5
0 to 200
%
ALWAYS
TECHNICIAN
01485
0484 Seq Stop Method VHz
Setup::Motor Control::Control and Type
Parameters::Motor Control::Ramp
USINT
(enum)
1
0:DISABLED VOLTAGE
1:RAMP
2:STOP RAMP
3:DC INJECTION
ALWAYS
TECHNICIAN
01495
0485 Ramp Type
Parameters::Motor Control::Ramp
USINT
(enum)
0
0:LINEAR
1:S RAMP
ALWAYS
TECHNICIAN
01497
0486 Acceleration Time
Same as PNO 484
TIME
10.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01499
0487 Deceleration Time
Same as PNO 484
TIME
10.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01501
0488 Symmetric Mode
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN
01503
0489 Symmetric Time
Parameters::Motor Control::Ramp
TIME
10.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01505
0490 Sramp Continuous
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN
01507
0491 Sramp Acceleration
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s² ALWAYS
OPERATOR
01509
0492 Sramp Deceleration
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s² ALWAYS
TECHNICIAN
01511
0493 Sramp Jerk 1
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³ ALWAYS
TECHNICIAN
01513
0494 Sramp Jerk 2
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³ ALWAYS
TECHNICIAN
01515
0495 Sramp Jerk 3
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³ ALWAYS
TECHNICIAN
01517
0496 Sramp Jerk 4
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³ ALWAYS
TECHNICIAN
01519
0497 Ramp Hold
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN
01521
0498 Ramping Active
Parameters::Motor Control::Ramp
BOOL
NEVER
TECHNICIAN
01523
0499 Ramp Spd Setpoint Input
Parameters::Motor Control::Ramp
REAL
x.x
-200.0 to 200.0
%
NEVER
TECHNICIAN
01525
0500 Ramp Speed Output
Parameters::Motor Control::Ramp
REAL
x.x
-200.0 to 200.0
%
NEVER
TECHNICIAN
01527
0501 Jog Setpoint
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%
ALWAYS
TECHNICIAN
01529
0502 Jog Acceleration Time
Parameters::Motor Control::Ramp
TIME
1.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01531
0503 Jog Deceleration Time
Parameters::Motor Control::Ramp
TIME
1.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01533
0504 Stop Ramp Time
Same as PNO 484
TIME
10.000
0.000 to 600.000
s
ALWAYS
TECHNICIAN
01535
0505 Zero Speed Threshold
Parameters::Motor Control::Ramp
REAL
0.1
0.0 to 100.0
%
ALWAYS
TECHNICIAN
01537
0506 Zero Speed Stop Delay
Parameters::Motor Control::Ramp
TIME
0.500
0.000 to 30.000
s
ALWAYS
TECHNICIAN
01539
0507 Quickstop Time Limit
Parameters::Motor Control::Ramp
TIME
30.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01541
0508 Quickstop Ramp Time
Parameters::Motor Control::Ramp
TIME
0.100
0.000 to 600.000
s
ALWAYS
TECHNICIAN
01543