Appendix Function Parameter List
17
7
■
External Fault Stop Function
Signal input terminal for applying fault stop (emergency stop) to the inverter
through external devices can be set.
・
The inverter will stop output immediately after the external fault stop input
(setting value = 4) turns SW signal ON and “AU” is displayed.
・
Input signal logic setting (contact A and B input select) can be set with “P041:
Input Logic Setting”.
< Example > When SW1 (parameter P036 = 4) is set to external fault stop,
and input logic setting (P041 = 1) and run command select (parameter P003 =
2) are used
* When external fault stop signal is set to contact B input, fault reset can be
applied after run signal is turn OFF, even if external stop signal is “ON”. But
fault trip will occur after the run signal is turned “ON” again. So please turn the
run signal “ON” after the external fault stop signal being turned “OFF” for
normal operation.
■
Parameter Setting Disable Function
The signal input terminal for disabling the parameter setting through external
control can be set.
・
After signal input is turned ON, setting parameters with the operation panel
and communication are disabled.
・
When the signal input is turned ON, function parameters and built-in memory
parameters cannot be set but be monitored.
・
During data setting, data cannot be changed even if SET button is pressed
when the signal is ON.
Summary of Contents for VF200
Page 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Page 2: ......
Page 7: ......
Page 8: ...1 Safety Precautions ...
Page 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Page 15: ...Safety Precautions 8 ...
Page 16: ...9 Points for Handling Special Precautions 10 ...
Page 19: ...Points for Handling ...
Page 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Page 29: ...2 Installation 22 VF200 ...
Page 49: ...42 ...
Page 56: ...4 Operation Method Basic Operation ...
Page 75: ...4 Operation Method Basic Operation ...
Page 101: ...6 Function Parameters 94 ...
Page 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Page 107: ...7 Custom Mode 100 ...
Page 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Page 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Page 127: ...9 Troubleshooting 120 ...
Page 145: ...11 Specifications 138 ...
Page 146: ...139 Appendix Function Parameter List ...