Appendix Function Parameter List
248
P132
Motor Constant Measuring Function
・
During vector control or when auto torque boost or slip compensation is
performed through V/F control, motor constant can be set through “automatic
tuning” or specified as values recommended by our company.
・
When automatic tuning of voltage compensation
constant starts, the inverter will automatically apply
DC high-voltage to the motor. Therefore, do not
approach the unit.
Failure to do so may result in electric shock.
・
When automatic tuning of slip compensation freuqncy
starts, the inverter will drive the motor at 60 Hz.
Therefore, do not approach the unit.
Failure to do so may result in injury.
Setting value
Details
0
It indicates the value in normal status.
* The value is set in case that automatic tuning mode status for setting
value “1” and “2” is cancelled.
1
When voltage compensation constant is set to automatic tuning mode:
When the inverter returns to operation status display mode and enters
measurement status after data setting, the constant measurement can
be started by pressing RUNSW button.
2
When slip compensation constant is set to automatic tuning mode:
When the inverter returns to operation status display mode and enters
measurement status after data setting, the constant measurement can
be started by pressing RUNSW button.
3
Constants recommended by our company will be assigned to “P133:
Voltage Compensation Constant” and “P134: Slip Compenstion
Frequency” according to the setting values of “P130: Motor Capacity”
and “P131: Motor Pole Number”. (If constants for P133 and P134 are
changed after data setting, the setting value will become “0”
automatically.)
・
Please perform automatic tuning when the motor is fully stopped.
・
Please perform automatic tuning of slip compensation frequency when
there is no load on the motor shaft.
・
Acceleration time for automatic tuning of slip compensation frequency can
Summary of Contents for VF200
Page 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Page 2: ......
Page 7: ......
Page 8: ...1 Safety Precautions ...
Page 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Page 15: ...Safety Precautions 8 ...
Page 16: ...9 Points for Handling Special Precautions 10 ...
Page 19: ...Points for Handling ...
Page 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Page 29: ...2 Installation 22 VF200 ...
Page 49: ...42 ...
Page 56: ...4 Operation Method Basic Operation ...
Page 75: ...4 Operation Method Basic Operation ...
Page 101: ...6 Function Parameters 94 ...
Page 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Page 107: ...7 Custom Mode 100 ...
Page 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Page 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Page 127: ...9 Troubleshooting 120 ...
Page 145: ...11 Specifications 138 ...
Page 146: ...139 Appendix Function Parameter List ...