Appendix Function Parameter List
14
4
P004
Frequency Setting Signal
The frequency setting signal can be selected with operation panel, signal
input from external devices or communication command.
Setting
value
Command
status
Details of signal
setting
Operation method and control circuit terminal
connection diagram
0
Potentiometer
setting
Potentiometer on the panel
MAX: maximum frequency (refer to P005 and
P008)
MIN: minimum frequency (or 0 V stop)
OP trip will occur if the operation panel is
removed during operation.
1
Panel
Digital setting
Can be set in “Frequency Setting Mode (Fr)”
2
Potentiometer
Terminal No.13, 14 and 15 (center of
potentiometer is connected to No.14)
3
0 to 5 V
(Voltage signal)
Terminal No.14 and 15 (14: +, 15: -)
4
0 to 10 V
(Voltage signal)
Terminal No. 14 and 15 (14: +, 15: -)
5
4 to 20 mA
(Current signal)
Terminal No.14 and 15 (14: +, 15: -): a 200
Ω
resistor is connected between 14 and 15.
6
External
Control
0 to 20 mA
(Current signal)
Terminal No.14 and 15 (14: +, 15: -): a 200
Ω
resistor is connected between 14 and 15.
7
Communication
RS485
communication
Make frequency command transmitted through
communication valid.
8
Panel
Potentiometer
setting
Potentiometer on the operation panel
MAX: maximum frequency (refer to P005 and
P008)
MIN: minimum frequency (or 0 V stop)
*Operation will continue even if the panel is
removed during operation.
・
If a 4 to 20 mA or 0 to 20 mA signal is used, please connect a “200
Ω
resistor” between terminal No.14 and 15.
(If the 200
Ω
resistor is not connected, the inverter could be damaged.)
・
When frequency setting signal is set to a value other than “1” or “7”, the
Summary of Contents for VF200
Page 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Page 2: ......
Page 7: ......
Page 8: ...1 Safety Precautions ...
Page 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Page 15: ...Safety Precautions 8 ...
Page 16: ...9 Points for Handling Special Precautions 10 ...
Page 19: ...Points for Handling ...
Page 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Page 29: ...2 Installation 22 VF200 ...
Page 49: ...42 ...
Page 56: ...4 Operation Method Basic Operation ...
Page 75: ...4 Operation Method Basic Operation ...
Page 101: ...6 Function Parameters 94 ...
Page 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Page 107: ...7 Custom Mode 100 ...
Page 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Page 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Page 127: ...9 Troubleshooting 120 ...
Page 145: ...11 Specifications 138 ...
Page 146: ...139 Appendix Function Parameter List ...