Appendix Function Parameter List
238
■
Bias signal of PID control (setting value = “2”)
・
The 2
nd
analog input terminal can be used as measured value of PID control
(bias signal).
・
Input signals (0 to 5 V, 0 to 10 V, 4 to 20 mA and 0 to 20 mA) are fed back as
bias signal of PID control (setting example: -10% to +10%).
・
Bias value can be converted inside the inverter with parameter “P126: The
2
nd
Bias Frequency Setting”, “P127: The 2
nd
Gain Frequency Setting” and
“P157: The 2
nd
Analog Superimposed Value Setting”.
<Example> When the analog input ranges from 0 to 5 V and both the 2
nd
bias
value and the 2
nd
gain are set to “10”
・
After parameter P124 is set to “2”, set target value (SP) to the output
frequency through parameter “P004: Frequency Setting Signal” to perform
PID control that approaches target value SP depending on the bias signal
input to the analog input terminals. The output frequency will also be changed
accordingly. In this case, the inverter’s output frequency is determined by the
following formula.
Output frequency = Max. output frequency
×
(The 1
st
frequency setting signal
(%) + bias signal (%))
・
The value of the 1
st
frequency setting signal (%) depends on the value of
parameter “P004: Frequency Setting Signal”.But when parameter “P004:
Frequency Setting Signal” is specified as “1” or “7”, parameter “P111: PID
Target Value” can be used.
・
Parameters for PID control can be set with parameter P106 to P111.
Summary of Contents for VF200
Page 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Page 2: ......
Page 7: ......
Page 8: ...1 Safety Precautions ...
Page 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Page 15: ...Safety Precautions 8 ...
Page 16: ...9 Points for Handling Special Precautions 10 ...
Page 19: ...Points for Handling ...
Page 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Page 29: ...2 Installation 22 VF200 ...
Page 49: ...42 ...
Page 56: ...4 Operation Method Basic Operation ...
Page 75: ...4 Operation Method Basic Operation ...
Page 101: ...6 Function Parameters 94 ...
Page 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Page 107: ...7 Custom Mode 100 ...
Page 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Page 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Page 127: ...9 Troubleshooting 120 ...
Page 145: ...11 Specifications 138 ...
Page 146: ...139 Appendix Function Parameter List ...