Appendix Function Parameter List
232
●
Please use the inverter in the following conditions when set to “auto torque
boost”.
・
The motor must be the squirrel-cage induction motor for general purpose.
・
Please select the inverter with the capacity equivalent to or 1 level higher
than motor capacity.
Example 1) Please select a 0.75 kW inverter for motor ranging from 0.4 kW
to 0.75 kW.
Example 2) Please select a 1.5 kW inverter for motor ranging from 0.75 kW
to 1.5 kW.
・
The motor must be a 2-pole, 4-pole or 6-pole one.
・
It must be operated under standalone mode (i.e., one motor is driven by
one inverter).
・
The maximum wiring length between the inverter and motor must not
exceed 30 m.
If the above conditions are not satisfied, sound operation performance cannot
be achieved.
When vector control is selected, the output frequency ranges from 1 Hz to 120
Hz.
・
During auto torque boost setting, the output frequency ranges from 1 Hz to
120 Hz.
Related parameters: P005, P008, P036 to P040, P116, P118 to P123
Summary of Contents for VF200
Page 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Page 2: ......
Page 7: ......
Page 8: ...1 Safety Precautions ...
Page 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Page 15: ...Safety Precautions 8 ...
Page 16: ...9 Points for Handling Special Precautions 10 ...
Page 19: ...Points for Handling ...
Page 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Page 29: ...2 Installation 22 VF200 ...
Page 49: ...42 ...
Page 56: ...4 Operation Method Basic Operation ...
Page 75: ...4 Operation Method Basic Operation ...
Page 101: ...6 Function Parameters 94 ...
Page 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Page 107: ...7 Custom Mode 100 ...
Page 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Page 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Page 127: ...9 Troubleshooting 120 ...
Page 145: ...11 Specifications 138 ...
Page 146: ...139 Appendix Function Parameter List ...