4-5
Section
Host Link Commands
300
Response Format
An end code of 00 indicates normal completion.
@
K
C
x 10
0
x 10
1
x 16
1
x 16
0
↵
Node no.
Header
code
Terminator
FCS
End code
4-5-26 PC MODEL READ – MM
Reads the model type of the PC.
Command Format
@
M
M
x 10
0
x 10
1
↵
Node no.
Header
code
Terminator
FCS
Response Format
An end code of 00 indicates normal completion.
@
M
M
x 10
0
x 10
1
x 16
1
x 16
0
↵
x 16
1
x 16
0
Node no.
Header
code
Terminator
FCS
End code
Model
code
Parameters
Model Code
“Model code” indicates the PC model in two digits hexadecimal.
Model code
Model
01
C250
02
C500
03
C120
0E
C2000
10
C1000H
11
C2000H/CQM1/CPM2A/CPM2C/CPM1/CPM1A/SRM1(-V2)
12
C20H/C28H/C40H/C200H/C200HS
20
CV500
21
CV1000
22
CV2000
40
CVM1-CPU01-E
41
CVM1-CPU11-E
42
CVM1-CPU21-E
4-5-27 TEST – TS
Returns, unaltered, one block of data transmitted from the host computer.
Command Format
@
T
S
x 10
0
x 10
1
↵
Node no.
Header
code
Characters
122 characters max.
Terminator
FCS