2-5
Section
CPM2A/CPM2C Pulse Output Functions
100
Up/Down Pulse Outputs
•
For CW output:
Pulses output from output number 01000 (Word 010, bit 00).
•
For CCW output:
Pulses output from output number 01001 (Word 010, bit 01).
01000
CW operation
01001
CCW operation
•
Output mode: Continuous and Independent
•
Number of pulses: 1 to 16,777,215
•
Instructions:
PULS(65) and ACC(––)
•
With PULS(65), the number of pulses is set (in independent mode only).
•
With ACC(––), the output mode, starting frequency, target frequency, and
acceleration/deceleration rate are set, and the pulse outputs are started.
From when the pulse outputs are started until they are stopped, they are
controlled at a constant-ratio frequency change.
Independent Mode
Instruction execution: PULS(65) + ACC(––) (Independent mode)
Pulse output frequency
Target
frequency
Starting
frequency
0 Hz
Acceleration
Start
ACC(––)
Deceleration
Time
In independent mode, deceleration is
carried out at the acceleration/
deceleration rate in effect at the start.
Continuous Mode
Instruction execution: ACC(––) (Continuous mode)
Pulse output frequency
Target
frequency 2
0 Hz
Acceleration/
deceleration
Start
ACC(––)
Time
Target
frequency 3
Target
frequency 1
Acceleration/deceleration
Acceleration/deceleration
Acceleration or
deceleration
ACC(––)
Acceleration or
deceleration
ACC(––)