5-3
Section
I/O Allocation for CPM2C PCs
323
Example: Configuration Including Temperature Sensor Unit with 4 Inputs and CompoBus/S Link Unit
36 inputs
IR 00000 to IR 00011
IR 00100 to IR 00111
IR 00200 to IR 00211
Inputs
IR 000
IR 001
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Outputs
IR 010
IR 011
Do not use
2 temperature inputs
Input 0: IR 003
Input 1: IR 004
Input 2: IR 005
Input 3: IR 006
CPU Unit
(60 I/O points)
Temperature Sensor Unit
CPM1A-TS002/102
Do not use
8 inputs
IR 00700 to IR 00707
CompoBus/S I/O Link Unit
CPM1A-SRT21
IR 012
IR 013
Do not use
Used for input 0 of the Temperature Sensor Unit
Used for input 1 of the Temperature Sensor Unit
IR 002
IR 003
IR 004
24 outputs
IR 01000 to IR 01007
IR 01100 to IR 01107
IR 01200 to IR 01207
No outputs
8 outputs
IR 01300 to IR 01307
Used for input 1 of the Temperature Sensor Unit
Used for input 1 of the Temperature Sensor Unit
IR 005
IR 006
IR 007
Do not use
Bits
Only one 4-input Temperature Sensor Unit (CPM1A-TS002/102) can be con-
nected to the PC. The CPM1A-TS002/102 can, however, be connected together
with an Expansion I/O Unit or a different Expansion Unit.
5-3
I/O Allocation for CPM2C PCs
5-3-1 CPU Units
No. of I/O
(on CPU Unit)
Model number
I/O
Allocated bits
Max. No. of
Expansion I/O
Units
Max. No. of I/O
(see note 1)
10
CPM2C-10C
D
-D
Inputs
6 inputs: 00000 to 00005
5
170
Outputs 4 outputs: 01000 to 01003
20
CPM2C-20C
D
-D
Inputs
12 inputs: 00000 to 00011
5
180
Outputs 8 outputs: 01000 to 01007
32
CPM2C-32CDT
-D
Inputs
16 inputs: 00000 to 00007
and 00100 to 00107
5
192
Outputs 16 outputs: 01000 to 01007
and 01100 to 01107
Note
1. The values for the maximum number of I/O in the above table include the I/O
on Expansion I/O Units.
2. Although only up to 5 Expansion Units or Expansion I/O Units can be con-
nected to a CPM2C PC, no more than 10 input words and 10 output words
can be allocated.