Additional Information
Network Configuration Verification
The network configuration information is verified against the actual network when the EtherCAT
master is started. If an inconsistency is found during verification, a
Network Configuration
Verification Error
(84220000 hex) or
Network Configuration Verification Error (Mismatched
Slave)
(84330004 hex) event will occur.
Verified information
Required/optional
Description
Number of slaves connected Required
Number of slaves in the network
Vendor ID
Required
Vendor ID of each slave
Product code
Required
Product code of each slave
Revision
Optional
Revision number of each slave
Serial number
Optional
Serial numbers of all slaves
*1.
Set this by the
Revision Check Method
and
Serial Number Check Method
in the EtherCAT mas-
ter settings. You cannot set this setting for each slave.
5 Setting Up EtherCAT Communications with the Sysmac Studio
5-19
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
5-4
EtherCA
T Master Parameter Settings
5
Summary of Contents for NJ101-10 Series
Page 10: ...Manual Structure 8 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 80: ...3 EtherCAT Communications 3 12 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 236: ...9 Troubleshooting 9 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 274: ...Appendices A 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 275: ...I Index I 1 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505 I...
Page 279: ......