5. The slave receives the send frame of the process data from the EtherCAT master in the scheduled
trigger timing, and outputs data to relays and other output devices.
Calculation Formula for Maximum I/O Response Time
The maximum I/O response time is calculated for each periodic task of the CPU Unit in which I/O is
refreshed for EtherCAT slaves.
The formula for calculating the maximum I/O response time is as follows:
Maximum I/O response time =
Task period of periodic task (= process data communications cycle) × 2
+ Slave input response time + Slave output response time
+ Transmission delay time + Transmission jitter
Precautions for Correct Use
The values that are found in the above formula are guidelines instead of guaranteed values.
You must use a physical device to check the performance before the actual operation.
The following describes how to find each element value in the formula.
Task Period of Periodic Task
This indicates the task period of the primary periodic task or the priority-5 periodic task. The priori-
ty-5 periodic task is applicable only when you use an NX701 CPU Unit.
Transmission Delay Time
The following methods are provided to calculate the transmission delay times for the CPU Unit and
the periodic tasks in which I/O is refreshed.
Precautions for Correct Use
The calculation of the transmission delay times described below assume that OMRON slaves
are used with recommended cables.
CPU Unit
Periodic task of the CPU Unit in
which I/O is refreshed
Calculation method
NX701
Primary periodic task
•
Calculation with the Sysmac
Studio
•
Calculation by a formula
Priority-5 periodic task
Calculation with the Sysmac Stu-
dio
NX102 and NX1P2
Primary periodic task
•
Calculation with the Sysmac
Studio
•
Calculation by a formula
NJ-series
Calculation by a formula
1. Calculation with the Sysmac Studio
You can use the Sysmac Studio to display the transmission delay time for the EtherCAT master.
Refer to
Displaying Transmission Delay Time for EtherCAT Master with the Sysmac Studio
page 6-14 for details on this display method.
2. Calculation by a formula
6 Process Data Communications and SDO Communications
6-12
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
Summary of Contents for NJ101-10 Series
Page 10: ...Manual Structure 8 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 80: ...3 EtherCAT Communications 3 12 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 236: ...9 Troubleshooting 9 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 274: ...Appendices A 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 275: ...I Index I 1 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505 I...
Page 279: ......