5
Click the
Stop
Button to stop monitoring packets.
Saving Packet Data
Reading Data from the Sysmac Studio
After you stop packet monitoring, you can use the Sysmac Studio to read the packet data and save
it in a file.
1
Stop monitoring packets.
2
Click the
Save Packet Data
Button to save the packet data.
The
Save
Dialog Box is displayed.
3
Input a file name, and then click the
Save
Button.
A TCPDump packet data file with a .cap extension is saved.
Saving to an SD Memory Card from Memory in the CPU Unit
Stop monitoring packets, and then execute the EC_SaveMon (Save EtherCAT Packets) instruction
to save a given quantity of collected packet data in memory in the CPU Unit.
Then, execute the EC_CopyMon (Transfer EtherCAT Packets) instruction to save the packet data
that was saved in the CPU Unit to a file on an SD Memory Card inserted into the CPU Unit.
You can specify the name of the file that is saved in the SD Memory Card. The number of files is
limited only by the space that is available on the SD Memory Card.
Additional Information
• Packet data in the CPU Unit's memory is not retained when the power is interrupted.
• Packet data cannot be saved while packets are being monitored.
• Packet monitoring cannot be started while saving packet data.
• If an SD Memory Card is not inserted and you execute the instruction to copy the data to the
SD Memory Card, then an error is returned. If there is no SD Memory Card, only the one file
in the CPU Unit's memory can be read to the Sysmac Studio.
• Packet monitoring starts when the power is turned ON.
Appendices
A-9
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
A-2 Monitoring Packets
A
Summary of Contents for NJ101-10 Series
Page 10: ...Manual Structure 8 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 80: ...3 EtherCAT Communications 3 12 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 236: ...9 Troubleshooting 9 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 274: ...Appendices A 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Page 275: ...I Index I 1 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505 I...
Page 279: ......