28
Screen Titles
Section 5-2
5-2
Screen Titles
Screen titles are assigned to each screen that is built, as shown in the follow-
ing table.
5-3
Tuning Screen Realtime Trends
Up to 100 Tuning Screens for system version 4 or later and up to 32 Tuning
Screens for other system versions can be built using the Face Plate Auto-
Builder for NS. The NS-series data log is also generated for creating a real-
time trend graph for the Tuning Screens. Up to 100 data logs for system ver-
sion 4 or later and up to 32 data logs for other system versions are used and
data logs are created from the following details, according to the order the
face plates are built.
• Data log setting group name: Group (number) (Example: Group 1, Group
2, etc.)
• Data collection cycle: 1 s
• Log count: 533 records
• Log period: Logging is performed while data log object is displayed only.
(It is cleared when screens are switched.)
• Log address: (Refer to information on individual function blocks for details
on logging the SP, MV, and PV for the tag ITEM.)
Note
The NS project file built with the Face Plate Auto-Builder for NS create build-
ing results after returning the communications settings, unit and scale setting,
and data log settings to the default values for creating new projects. Specify a
new project name in the name for the project file being built.
5-4
Engineering Units
Values such as the SP and PV for Basic PID must be scaled to engineering
units.
In the following explanations, places where engineering units are indicated
must be scaled as defined in this section.
With the data in tag ITEMs for engineering units, such as PV and SP for Basic
PID, the value stored and used in the PLC or in communications for the scal-
ing lower limit (0%) is 0, and for the scaling upper limit (100%) is 10,000 (e.g.,
5,000 for scaling of 50%,
−
1,500 for
−
15%, etc.).
When the value of a tag ITEM for an engineering unit is displayed or set on
the PT screen, the value must be displayed or set as the actual amount (engi-
neering unit value) after scaling.
Scaling is performed by referencing the CSV tag file's scaling upper limit, scal-
ing lower limit, decimal point position (scaling decimal point position), and unit
characters.
Screen
Screen title assignment method
Control Screens
Control Screen
<Sequential number from 1>
Example: Control Screen 1, Control Screen 2, etc.
Tuning Screens
Tuning Screen - <
Tag No.>
Tag No.
Example: Tuning Screen
−
TIC0000.
Summary of Contents for Face Plate Auto-Builder for NS 3.1
Page 2: ...WS02 NSFC1 EV3 Face Plate Auto Builder for NS Ver 3 1 Operation Manual Revised December 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 21: ...6 Upgrades Made for Version 3 1 Section 1 6...
Page 27: ...12 Uninstalling the Face Plate Auto Builder for NS Section 2 2...
Page 28: ...13 SECTION 3 Basic Operation Flow 3 1 Basic Operation Flow 14...
Page 39: ...24 Merging Projects Section 4 2...
Page 141: ...126 Segment Program 3 Block Model 158 Section 6 19...
Page 143: ...128 Revision History...