105
Blended PID (Block Model 013)
Section 6-17
6-17-2 Tuning Screens
This section describes only the differences between the tuning screens in the
Blended PID Block and Basic PID Block (Block Model 011). For details on the
areas not covered here, refer to
6-1-2 Tuning Screens
.
1: Parameter Settings
These fields are used to display and set each parameter for blended PID con-
trol.
Numeral Display and Input objects are used to create these fields, and a ten-
key pad is displayed when a field is touched.
The following table shows the upper and lower limits of the setting ranges.
Parameter
Referenced tag ITEM
Cumulative deviation output
DEV_Q (044)
Ratio
K1 (027)
Accumulated value
Rightmost 4 digits: Q1 (012)
Leftmost 4 digits: Q2 (013)
(The addresses set in the object are working
addresses.)
Proportional band
P (054)
Integral time
I (055)
Differential time
D (056)
MH (High MV limit)
MH_LMT (076)
ML (Low MV limit)
ML_LMT (077)
MV index position
MV_IDX (098)
Parameter
Lower limit
Upper limit
Cumulative deviation output
−
32000
32,000
Ratio
0
3.2000
Accumulated value
(Cannot be input.)
(Cannot be input.)
Proportional band
0.1
999.9
Integral time
0
9999
1
2
Summary of Contents for Face Plate Auto-Builder for NS 3.1
Page 2: ...WS02 NSFC1 EV3 Face Plate Auto Builder for NS Ver 3 1 Operation Manual Revised December 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 21: ...6 Upgrades Made for Version 3 1 Section 1 6...
Page 27: ...12 Uninstalling the Face Plate Auto Builder for NS Section 2 2...
Page 28: ...13 SECTION 3 Basic Operation Flow 3 1 Basic Operation Flow 14...
Page 39: ...24 Merging Projects Section 4 2...
Page 141: ...126 Segment Program 3 Block Model 158 Section 6 19...
Page 143: ...128 Revision History...