20
Basic Operation
Section 4-1
2.
Set the required items. The settings and display is described in the follow-
ing table.
Step 4: Load the
Project File
Use CX-Designer to read the automatically built project files.
Use CX-Designer to edit the project files as required.
Step 5: Transfer the
Settings to the NS-
series PT
Transfer the settings from CX-Designer to the NS-series PT (or save the set-
tings to a Memory Card and install the Memory Card in the NS-series PT).
Start the system, and perform monitoring/tuning of the Loop Control Unit/
Board from the NS-series PT.
Note
An error message saying that the file is too large and to check the product
data (0088) may be displayed when transferring a project from the CX-
Designer to the NS-series PT. If this message appears, clear the selection of
Item
Meaning
CSV tag file
settings
Network
address
Displays the network address given in the CSV tag
file.
Node address
Displays the node address given in the CSV tag file.
Settings reg-
istered in
CX-Designer
Communica-
tions connec-
tion method
Set the node (host) connection method.
Any of the following three methods can be set: Serial
port A, serial port B, Ethernet/CLK
Example: If the node is connected to serial port A,
select Serial port A.
Note: The host name, network address, and node
address cannot be set if serial port A or serial B is
selected.
• Serial Port A Settings
Host name: SERIALA
Network address: 111
Node address: 1
• Serial port B Settings
Host name: SERIALB
Network address: 112
Node address: 1
Note: When Ethernet/CLK is selected, the PLC type
registered in the CX-Designer will always be SYS-
MAC-CS1.
Host name
Set the host name.
• The host name must be all-caps.
• The host name can be up to 16 characters long.
• The same host name can be used only once.
• The host name, network address, and node
address cannot be set if serial port A or serial B is
selected as the communications connection
method.
Network
address
Set the network address of the node (host) as viewed
from the NS-series PT.
The network address will be 111 or 112 if serial port
A or serial B is selected as the communications con-
nection method.
Node address
Set the node address of the node (host) as viewed
from the NS-series PT.
The node address will be 1 if serial port A or serial B
is selected as the communications connection
method.
Summary of Contents for Face Plate Auto-Builder for NS 3.1
Page 2: ...WS02 NSFC1 EV3 Face Plate Auto Builder for NS Ver 3 1 Operation Manual Revised December 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 21: ...6 Upgrades Made for Version 3 1 Section 1 6...
Page 27: ...12 Uninstalling the Face Plate Auto Builder for NS Section 2 2...
Page 28: ...13 SECTION 3 Basic Operation Flow 3 1 Basic Operation Flow 14...
Page 39: ...24 Merging Projects Section 4 2...
Page 141: ...126 Segment Program 3 Block Model 158 Section 6 19...
Page 143: ...128 Revision History...