43
Basic PID (Block Model 011)
Section 6-1
1: Status
This button is used to switch between the statuses for Stop Block Operation
Command (tag ITEM MT_ST (ITEM 000)), Alarm Stop Switch (tag ITEM AOF
(ITEM 017)), and AT Command/AT Executing (tag ITEM AT (ITEM 035)).
Each button is built as an alternate ON/OFF Button, and using an Alternate
Simple Rectangle (Type 2), as shown in the following table.
The read address is set as the display address and the write address is set as
write address 1.
2: Alarm Set Values
The alarm set values are displayed and set with engineering units. The follow-
ing table shows the tag ITEMs used for setting alarm set values.
Numeral Display and Input objects are used to create these fields, and a ten-
key pad is displayed when a field is touched. The following table shows the
upper and lower limits of the setting ranges.
The engineering unit displayed for the unit as a Text object.
Data is written to the write address of each tag ITEM using the Before Writing
Numeral/String macro.
Button
Tag
ITEM
Color
(OFF)
Color
(ON)
Label
(OFF)
Label
(ON)
Write
confirmation
message
Stop block
operation
command
MT_ST
(ITEM
000)
Gray
Yellow
Operating
Operation
stopped
Yes
“OK?”
Alarm
stop
switch
AOF
(ITEM
017)
Gray
Yellow
Alarm ON
Alarm dis-
abled
Yes
“OK?”
AT com-
mand/ AT
executing
AT
(ITEM
035)
Gray
Yellow
AT OFF
AT ON
Yes
“The MV will
change is AT is
executed/stopped.
OK?”
Alarm type
Alarm set value tag ITEM
LL (Low/low alarm)
LL_SP (ITEM 011)
L (Low alarm)
L_SP (ITEM 010)
H (High alarm)
H_SP (ITEM 009)
HH (High/high alarm)
HH_SP (ITEM 008)
DV (Deviation alarm)
DVA_SP (ITEM 041)
Alarm type
Upper limit
Lower limit
LL (Low/low alarm)
−
15% in the corresponding
engineering units
115% in the corresponding
engineering units
L (Low alarm)
−
15% in the corresponding
engineering units
115% in the corresponding
engineering units
H (High alarm)
−
15% in the corresponding
engineering units
115% in the corresponding
engineering units
HH (High/high
alarm)
−
15% in the corresponding
engineering units
115% in the corresponding
engineering units
DV (Deviation alarm) 0% in the corresponding engi-
neering units
115% in the corresponding
engineering units
Summary of Contents for Face Plate Auto-Builder for NS 3.1
Page 2: ...WS02 NSFC1 EV3 Face Plate Auto Builder for NS Ver 3 1 Operation Manual Revised December 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 21: ...6 Upgrades Made for Version 3 1 Section 1 6...
Page 27: ...12 Uninstalling the Face Plate Auto Builder for NS Section 2 2...
Page 28: ...13 SECTION 3 Basic Operation Flow 3 1 Basic Operation Flow 14...
Page 39: ...24 Merging Projects Section 4 2...
Page 141: ...126 Segment Program 3 Block Model 158 Section 6 19...
Page 143: ...128 Revision History...