5.3Settings for the safety PLC
5-6
9
Make the setting of "IO Connection". Select the "Connection" tab.
- Set the following values.
Item
Setting value
Input Assembly Instance
Set the value of "768 + (The value that is
set in the "Safety Input -> Size")
For example, is the Size is 8 bytes, input
776.
Output Assemble Instance
1024
Safety Input
Size
Set the size of the input data.
Because this is the setting of the input for
the PLC, set the value of "Output bytes" of
the RMU.
Input Assembly Instance
1024
Output Assemble Instance
Set the value of "896 + (The value that is
set in the "Safety Output -> Size")
Safety Output
Size
Set the size of the output data.
Because this is the setting of the output
from the PLC, set the value of "Input
bytes" of the RMU.
Configuration Assembly Instance
1024
- Press the "OK" button.
10
Select the "Safety" tab.
>> The following screen will show up.
- Set a value of 50ms or more for the " Safety Input
→
Requested Packet Interval (RPI)(ms)"
- Turn OFF the check box of "Configuration Signature"
- Press "OK" at last.
IMPORTANT
The minimum communication speed of the RMU is 50ms. However, depending on the
environment of the network (communication speed), there is a possibility in which the
RMU cannot respond in time. Setup the appropriate communication cycle of the network
and perform the risk assessment for the setting in advance.
Summary of Contents for RMU20-20
Page 2: ......
Page 6: ...Contents 4 ...
Page 8: ......
Page 26: ...1 4 EC DECLARATION OF CONFORMITY FOR MACHINERY 1 18 NOTE ...
Page 68: ...2 9 Enabling RMU 2 40 NOTE ...
Page 70: ......
Page 100: ...3 4 Setting when a slider unit is used 3 30 NOTE ...
Page 102: ......
Page 138: ...4 4Approval 4 36 8 Approval is completed The following screen will be displayed ...
Page 144: ......
Page 154: ...5 4Trouble shooting 5 10 NOTE ...
Page 156: ......
Page 166: ...6 4Trouble shooting 6 10 NOTE ...
Page 168: ......
Page 189: ......