5.3Settings for the safety PLC
5-4
5.3
Settings for the safety PLC
As an example of the Safety PLC setting, how to add a setting of RMU for the Rockwell Compact GuardLogix
L43S is shown hereinafter.
CAUTION
The procedures shown in this section are described mainly to change the settings.
Therefore, safety is not considered.
After completing the settings, do not forget to check that the settings are correct.
5.3.1
Setting procedure
1
Run the "RSLogix5000".
2
Select the "Controller project" of the network to which the RMU is added.
- To create new one, select [New] in the [File] menu.
- If a communication module is not installed in the Bus of the "I/O Configuration", add a
communication module e.g. "1768 ENBT" etc.
3
Right click the [Tasks] -> [SafetyTask] of the "Controller Organizer", and then select the
[Properties].
>> The following screen will show up.
4
Select the "Configuration" tab and input the value of "Period".
- For "Period", set a value of 50ms or more.
- After the setting, press "OK".
5
Right-click a communication module in the "Controller Organizer" and select "New Module".
>>"Select Module Type" screen will be displayed.
Summary of Contents for RMU20-20
Page 2: ......
Page 6: ...Contents 4 ...
Page 8: ......
Page 26: ...1 4 EC DECLARATION OF CONFORMITY FOR MACHINERY 1 18 NOTE ...
Page 68: ...2 9 Enabling RMU 2 40 NOTE ...
Page 70: ......
Page 100: ...3 4 Setting when a slider unit is used 3 30 NOTE ...
Page 102: ......
Page 138: ...4 4Approval 4 36 8 Approval is completed The following screen will be displayed ...
Page 144: ......
Page 154: ...5 4Trouble shooting 5 10 NOTE ...
Page 156: ......
Page 166: ...6 4Trouble shooting 6 10 NOTE ...
Page 168: ......
Page 189: ......