85
CHAPTER 7 VARIOUS SETTINGS
7
7.1 Parameter Sett
ing
6.
Click the
button to write the parameter to the high-speed counter module.
●
When using the extension module, also set the parameter of the extension module.
For the parameter of the extension module, refer to the following.
Manual for the extension module used
●
Set all the items for the parameter. If any blank exists, the parameter cannot be written to the high-speed counter module.
●
To read the parameter from the high-speed counter module, set "Parameter read" for "Method selection" and click the
button.
●
When the following message is displayed, take corrective action for the error code in <>. (
●
When the parameters are written, the contents in the extended parameter area are stored in the nonvolatile memory.
●
When writing the parameters while Initial data processing request flag (RX8) is off, set values in the remote registers
(RWw) beforehand. The values in the remote registers (RWw) related to the setting values of the parameters are
checked at the writing. If the setting is incorrect, an error occurs.
Z phase input response time setting
Setting
OFF
→
ON Response
time
ON
→
OFF Response
time
0
0.25µs
2.5µs
1
0.1ms
0.1ms
2
1.0ms
1.0ms
Function input response time setting
Setting
OFF
→
ON Response
time
ON
→
OFF Response
time
0
0.02ms
0.1ms
1
0.1ms
0.1ms
2
1.0ms
1.0ms
Latch counter input response time setting
Setting
OFF
→
ON Response
time
ON
→
OFF Response
time
0
0.02ms
0.1ms
1
0.1ms
0.1ms
2
1.0ms
1.0ms
Pulse measurement setting (Function
input terminal)
0: Pulse ON Width
1: Pulse OFF Width
Pulse measurement setting (Latch
counter input terminal)
0: Pulse ON Width
1: Pulse OFF Width
Setting item
Setting details
Reference
Summary of Contents for NZ2GFCF-D62PD2
Page 1: ......
Page 2: ......
Page 54: ...52 Memo ...
Page 206: ...204 Memo ...
Page 303: ......
Page 304: ......