101
CHAPTER 8 FUNCTIONS
8
8.2 C
ounter F
ormat Selectio
n
8.2.2 R
ing
counte
r functio
n
●
The setting values of CH
Ring counter upper limit value (RWw12 to RWw13, RWw2A to RWw2B) and CH
Ring
counter lower limit value (RWw10 to RWw11, RWw28 to RWw29) can be reflected by turning off then on Initial data
processing completion flag (RY8) or by turning off then on Initial data setting request flag (RY9). In that case, however,
monitoring data such as CH
Present value (RWr10 to RWr11, RWr28 to RWr29) is cleared. For ordinary use, reflect the
setting values by turning off then on CH
Count enable command (RY24, RY3C).
●
When CH
Count enable command (RY24, RY3C) is on, the stored value does not change even if a value is written to
CH
Ring counter lower limit value (RWw10 to RWw11, RWw28 to RWw29) and CH
Ring counter upper limit value
(RWw12 to RWw13, RWw2A to RWw2B).
Turn off CH
Count enable command (RY24, RY3C) before changing CH
Ring counter upper limit value (RWw12 to
RWw13, RWw2A to RWw2B) and CH
Ring counter lower limit value (RWw10 to RWw11, RWw28 to RWw29). The OFF
time must be longer than
Δ
T
1
.
For
Δ
T
1
, refer to Page 283, Appendix 4.
●
Always turn off CH
Count enable command (RY24, RY3C) before changing the counting range by the preset/replace
function to prevent a miscount.
Summary of Contents for NZ2GFCF-D62PD2
Page 1: ......
Page 2: ......
Page 54: ...52 Memo ...
Page 206: ...204 Memo ...
Page 303: ......
Page 304: ......