125
CHAPTER 8 FUNCTIONS
8
8.4 Pr
eset/
replace
Functio
n
(b) Operation example of the preset/replace function by CH
Phase Z input terminal
(Z1, Z2)
The following figure shows an operation example of turning on CH
External preset/replace (Z Phase) request
detection (RX23, RX3B) and changing the present value to the preset value (100) at the rising edge of CH
Phase Z input terminal (Z1, Z2).
No.
Description
1)
Write any value to CH
Preset value setting (RWw14 to RWw15, RWw2C to RWw2D) in 32-bit binary.
(Setting range: -2147483648 to 2147483647)
2)
The value in CH
Preset value setting (RWw14 to RWw15, RWw2C to RWw2D) is stored in CH
Present value (RWr10 to RWr11,
RWr28 to RWr29) at the rising edge (off to on) of CH
Phase Z input terminal (Z1, Z2). Also, CH
External preset/replace (Z
Phase) request detection (RX23, RX3B) turns on.
The value can be replaced regardless of the ON/OFF status of CH
Count enable command (RY24, RY3C).
3)
While CH
External preset/replace (Z Phase) request detection (RX23, RX3B) is on, the value cannot be replaced by either CH
Preset/replace command (RY21, RY39) or CH
Phase Z input terminal (Z1, Z2).
Also, when CH
Preset/replace command (RY21, RY39) is turned off then on, CH
Preset/replace completion (RX21, RX39)
turns on. However, the value is not replaced. Turn off CH
Preset/replace completion (RX21, RX39) by turning off CH
Preset/replace command (RY21, RY39).
4)
When CH
External preset/replace (Z Phase) request detection (RX23, RX3B) turns off by turning on CH
External preset/replace
(Z Phase) request detection reset command (RY23, RY3B), the value can be replaced.
CH Present value
(RWr10 to RWr11, RWr28 to RWr29)
CH Phase Z input terminal
(Z1, Z2)
CH External preset/replace
(Z Phase) request detection
(RX23, RX3B)
CH External preset/replace
(Z Phase) request detection
reset command (RY23, RY3B)
0
1
to 65
66
67
100
105
101
100 101
102
106 107
103 104
108 109
110
t T
1
2)
ON
ON
ON
ON
OFF
CH Preset/replace completion
(RX21, RX39)
OFF
2)
4)
Counter pulse
CH Preset/replace command
(RY21, RY39)
CH Preset value setting
(RWw14 to RWw15,
RWw2C to RWw2D)
CH Count enable command
(RY24, RY3C)
Controlled by the high-speed counter module
Controlled by the program
OFF
t
t
1)
ON
OFF
100
0
3)