249
APPENDICES
A
Appendix 1 Details of R
emote I/O Signa
ls
Appendix 1.2 Details of r
emote outp
ut signals
Appendix 1.2
Details of remote output signals
The following shows details of remote output signals.
Remote
output
(RY) No.
Signal name
Operation
timing
Description
RY8
Initial data processing
completion flag
• This signal is turned on when initial data processing has been completed after the
module is powered on, the remote reset is performed, or parameters are
initialized.
• When this signal is turned on, the high-speed counter module starts counting
regarding the content of the remote register (RWw) as the initial value.
(For the overview of the operation, refer to Page 236, Appendix 1.1.)
RY9
Initial data setting
request flag
• Turn on this signal to activate the setting data in the parameter area of the remote
buffer memory. Turn on this signal to save the setting values of the extended
parameter area into the nonvolatile memory.
• When this signal is turned on, the setting values in the parameter area of the
remote buffer memory are reflected to the inside of the module. In addition, the
setting values of the extended parameter area are saved into the nonvolatile
memory.
• When this signal is turned on, all the following remote input signals turn off.
• Warning status flag (RX7)
• Error status flag (RXA)
• Remote READY (RXB)
• Coincidence output 1 to 4 (RX10 to RX13)
• Setting change completed (Coincidence output 1 to 4) (RX14 to RX17)
• CH
Preset/replace completion (RX21, RX39)
• CH
External preset/replace (Z Phase) request detection (RX23, RX3B)
• CH
Counter function detection (RX25, RX3D)
• CH
Cam switch execute/PWM output (RX26, RX3E)
• CH
Setting change completed (Sampling counter/Periodic pulse counter)
(RX27, RX3F)
• CH
Update flag reset completed (Latch count value/Sampling count
value/Periodic pulse count value) (RX28, RX40)
• CH
Update flag (Latch count value/Sampling count value/Periodic pulse count
value) (RX29, RX41)
• CH
Latch count value update flag reset completed (Latch counter input
terminal) (RX2A, RX42)
• CH
Latch count value update flag (Latch counter input terminal) (RX2B,
RX43)
• CH
Update flag reset completed (Measured frequency value/Measured
rotation speed value) (RX2C, RX44)
• CH
Update flag (Measured frequency value/Measured rotation speed value)
(RX2D, RX45)
• CH
Measured pulse value update flag reset completed (Function input
terminal) (RX31, RX49)
• CH
Measured pulse value update flag (Function input terminal) (RX32, RX4A)
• CH
Measured pulse value update flag reset completed (Latch counter input
terminal) (RX33, RX4B)
• CH
Measured pulse value update flag (Latch counter input terminal) (RX34,
RX4C)
• CH
ON width setting change completed (PWM output) (RX35, RX4D)
• CH
Error status (RX36, RX4E)
• CH
Warning status (RX37, RX4F)
• External input signals of the extension input module (RX50 to RX5F)