121
CHAPTER 8 FUNCTIONS
8
8.3 C
ompariso
n Outp
ut Function
8.3.4 C
am sw
itch function
(5) Signal timing of the cam switch function
The following figure shows the signal timing of the cam switch function.
• Only Cam switch (Output 1) is used.
• Coincidence output 1 is assigned to CH1.
• "1: Stage 1" is assigned to "Cam switch output unit assignment setting".
• "0: CH1" is assigned to "Cam switch output 1 channel assignment setting".
*1
For
Δ
T
3
, refer to Page 283, Appendix 4.
Cam switch output signal (RWr2) turns on regardless of CH
Count enable command (RY24, RY3C).
No.
Description
1)
When CH1 Cam switch execute command (RY26) is turned off then on, the step setting of Cam switch (Output 1) is acquired and
CH1 Cam switch execute (RX26) turns on. (If the value is changed while the cam switch function is in operation, the change is
ignored.)
2)
The cam switch function operates when CH1 Cam switch execute (RX26) turns on.
3)
CH1 Present value (RWr10 to RWr11) and the step setting of Cam switch (Output 1) are compared and the result is output from Y0
of the extension output module. The output status can be checked by Cam switch status (Output 1) (RWr2.b0) of Cam switch output
signal (RWr2).
4)
When CH1 Cam switch execute command (RY26) is turned off, the operation is as follows:
• CH1 Cam switch execute (RX26) turns off.
• Cam switch status (Output 1) (RWr2.b0) becomes 0.
• Y0 of the extension output module is turned off.
External output signal of the extension
output module (Y0)
CH1 Cam switch execute command (RY26)
Cam switch status (Output 1) (RWr2.b0)
2)
4)
3)
ON/OFF status of Cam switch (Output 1)
4)
CH1 Cam switch execute (RX26)
4)
4)
3)
T
3*1
1)
Controlled by the high-speed counter module
Controlled by the program
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
1
1
OFF
ON
ON
1
ON
OFF
OFF
OFF
OFF
0
0
0
Summary of Contents for NZ2GFCF-D62PD2
Page 1: ......
Page 2: ......
Page 54: ...52 Memo ...
Page 206: ...204 Memo ...
Page 303: ......
Page 304: ......