110
(b) Operation example of within-range output
The following figure shows the timing to enable Lower limit value setting (Coincidence output 1) (1000) and
Upper limit value setting (Coincidence output 1) (2000) and an operation example of when the present value
reaches the setting range (1000 to 2000) for the case where within-range output is set as the comparison
condition. Note that Coincidence output 1 is assigned to CH1.
No.
Description
1)
Start comparison of the present value and values set to Lower limit value setting (Coincidence output 1) (RWw0 to RWw1) and
Upper limit value setting (Coincidence output 1) (RWw2 to RWw3) in the following order.
(1) Write 1000 into Lower limit value setting (Coincidence output 1) (RWw0 to RWw1).
(2) Write 2000 into Upper limit value setting (Coincidence output 1) (RWw2 to RWw3).
(3) Turn off then on Setting change request (Coincidence output 1) (RY14).
(4) The values set for Lower limit value setting (Coincidence output 1) (RWw0 to RWw1) and Upper limit value setting (Coincidence
output 1) (RWw2 to RWw3) are enabled when Setting change completed (Coincidence output 1) (RX14) turns on. After
confirming that Setting change completed (Coincidence output 1) (RX14) turns on, turn off Setting change request
(Coincidence output 1) (RY14).
2)
Turn off then on CH1 Count enable command (RY24) to start counting.
3)
If performing coincidence output from the coincidence output 1 terminal (EQU1), turn on CH1 Coincidence output enable command
(RY20).
4)
When CH1 Present value (RWr10 to RWr11) is Lower limit value setting (Coincidence output 1) (RWw0 to RWw1) or more and the
present value is within the specified range, Coincidence output 1 (RX10) and the coincidence output 1 terminal (EQU1) turn on.
5)
When CH1 Present value (RWr10 to RWr11) is more than Upper limit value setting (Coincidence output 1) (RWw2 to RWw3) and
the present value is outside the specified range, Coincidence output 1 (RX10) and the coincidence output 1 terminal (EQU1) turn
off.
Setting change request
(Coincidence output 1) (RY14)
Coincidence output 1 terminal (EQU1)
1)
Lower limit value setting
(Coincidence output 1)
(RWw0 to RWw1)
0
1000
Coincidence output 1 (RX10)
ON
ON
OFF
ON
OFF
ON
OFF
CH1 Present value (RWr10 to RWr11)
3)
4)
0
1
999 1000
2000 2001
5)
CH1 Count enable command (RY24)
CH1 Coincidence output
enable command (RY20)
ON
OFF
ON
OFF
Setting change completed
(Coincidence output 1) (RX14)
ON
OFF
Upper limit value setting
(Coincidence output 1)
(RWw2 to RWw3)
0
2000
4)
5)
2)
: Controlled by the high-speed counter module
: Controlled by the program