8.18
Cyclic Data Update Watch Function
This function monitors the cyclic data update interval. When the cyclic transmission remains to be stopped over the set
watch time, this function holds or clears the value which is output just before.
In the cyclic transmission stop status, the D LINK LED is flashing (Data link in operation (cyclic transmission stopped))
or off (Data link not performed (disconnected)).
Set whether to hold or clear the output value using the output HOLD/CLEAR setting function. For the output
HOLD/CLEAR setting function, refer to the following.
• Output HOLD/CLEAR Setting Function (
(1) Setting method
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select a high-speed counter module in "List of stations"
[CC IE Field Configuration]
[Parameter Processing of Slave Station]
2.
For "Cyclic data update watch time setting", set the monitoring time.
Set the greater value for the cyclic data update watch time setting than that of the link scan time.
Item
Setting range
Cyclic data update watch time setting
• 0 (Not monitor)
• 1 to 20 (0.1 to 2 seconds, in increments of 100ms)
Master station
Remote device station
The cyclic data are updated within
the data link update time.
Cyclic data
When the cyclic data update interval
exceeds the set time, the output falls
into the HOLD/CLEAR status.
Monitoring starts when cyclic data
are received for the first time.
Cyclic data update
watch time setting