220
815
H
Moderate error
Coincidence
output channel
assignment
setting error
The channel where the
PWM output mode is
selected is not assigned to
the setting in Coincidence
output channel
assignment setting
(address: 0101
H
).
indicates the channel
where settings are
incorrect.
*13
Assign the channel where the
PWM output mode is selected
on Coincidence output channel
assignment setting (address:
0101
H
), and turn off then on
Initial data setting request flag
(RY9).
820
H
Moderate error
CH
Counter
format setting
error
A value other than 0 and 1
is set in CH
Counter
format (address: 0124
H
,
0144
H
).
indicates the channel
where settings are
incorrect.
*13
Set CH
Counter format
(address: 0124
H
, 0144
H
) to 0 or
1, and turn off then on Initial
data setting request flag (RY9).
821
H
Moderate error
CH
Counter
function
selection setting
error
A value other than 0 to 5 is
set in CH
Counter
function selection
(address: 0126
H
, 0146
H
).
indicates the channel
where settings are
incorrect.
*13
Set CH
Counter function
selection (address: 0126
H
,
0146
H
) to a value between 0
and 5, and turn off then on
Initial data setting request flag
(RY9).
822
H
Moderate error
CH
Function
input logic
setting error
A value other than 0 and 1
is set in CH
Function
input logic setting
(address: 0127
H
, 0147
H
).
indicates the channel
where settings are
incorrect.
*13
Set CH
Function input logic
setting (address: 0127
H
,
0147
H
) to 0 or 1, and turn off
then on Initial data setting
request flag (RY9).
823
H
Moderate error
CH
Latch
counter input
logic setting
error
A value other than 0 and 1
is set in CH
Latch
counter input logic setting
(address: 0128
H
, 0148
H
).
indicates the channel
where settings are
incorrect.
*13
Set CH
Latch counter input
logic setting (address: 0128
H
,
0148
H
) to 0 or 1, and turn off
then on Initial data setting
request flag (RY9).
824
H
Moderate error
CH
Z phase
input response
time setting
error
A value other than 00b to
10b is set in CH
Z phase
input response time
setting (address: 0129
H
.b0
to b1, 0149
H
.b0 to b1).
indicates the channel
where settings are
incorrect.
*13
Set CH
Z phase input
response time setting (address:
0129
H
.b0 to b1, 0149
H
.b0 to
b1) to a value between 00b and
10b, and turn off then on Initial
data setting request flag (RY9).
825
H
Moderate error
CH
Function
input response
time setting
error
A value other than 00b to
10b is set in CH
Function input response
time setting (address:
0129
H
.b2 to b3, 0149
H
.b2
to b3).
indicates the channel
where settings are
incorrect.
*13
Set CH
Function input
response time setting (address:
0129
H
.b2 to b3, 0149
H
.b2 to
b3) to a value between 00b and
10b, and turn off then on Initial
data setting request flag (RY9).
Error code
(hexadecimal)
Classification
Error name
Description and
cause
Operation of when an error
occurs
Action
Error CH
The other
CHs
Summary of Contents for NZ2GFCF-D62PD2