CHAPTER 8 FUNCTIONS
8
8.3 C
ompariso
n Outp
ut Function
8.3.2 C
oincidence output fun
ction
●
Coincidence output 1 to 4 (RX10 to RX13) turn on regardless of CH
Coincidence output enable command (RY20,
RY38).
●
Set the ON time of Reset command (Coincidence output 1 to 4) (RY10 to RY13) to
Δ
T
1
or longer.
For
Δ
T
1
, refer to Page 283, Appendix 4.
●
Due to coincidence detection processing inside the high-speed counter module, the counter value greater or smaller
corresponding to Counter value greater/smaller signal (RWr0) is not updated at the same time when Coincidence output
1 to 4 (RX10 to RX13) turns off then on. Therefore, the counter value greater or smaller may be 1 even though it is not the
correct value.
●
Even if Point setting (Coincidence output 1 to 4) (RWw0 to RWw1, RWw4 to RWw5, RWw8 to RWw9, RWwC to RWwD)
is changed, the present value is not compared with the changed value unless Setting change request (Coincidence
output 1 to 4) (RY14 to RY17) is turned off then on.
No.
Description
1)
Start comparison of the present value and a value set to Point setting (Coincidence output 1) (RWw0 to RWw1) in the following
order.
(1) Write 1000 into Point setting (Coincidence output 1) (RWw0 to RWw1).
(2) Turn off then on Setting change request (Coincidence output 1) (RY14).
(3) The values set in Point setting (Coincidence output 1) (RWw0 to RWw1) are enabled when Setting change completed
(Coincidence output 1) (RX14) turns on. After confirming that Setting change completed (Coincidence output 1) (RX14) turns
on, turn off Setting change request (Coincidence output 1) (RY14).
2)
When CH1 Present value (RWr10 to RWr11) is less than Point setting (Coincidence output 1) (RWw0 to RWw1), the value in
Counter value smaller (Coincidence output 1) (RWr0.b0) is 1.
3)
When Reset command (Coincidence output 1) (RY10) is turned on, Coincidence output 1 (RX10) and the coincidence output 1
terminal (EQU1) turn off.
4)
Turn off then on CH1 Count enable command (RY24) to start counting.
5)
If performing coincidence output from the coincidence output 1 terminal (EQU1), turn on CH1 Coincidence output enable command
(RY20).
6)
When CH1 Present value (RWr10 to RWr11) equals to Point setting (Coincidence output 1) (RWw0 to RWw1), Coincidence output
1 (RX10) and the coincidence output 1 terminal (EQU1) turn on. Also, Counter value smaller (Coincidence output 1) (RWr0.b0)
becomes 0.
7)
If Reset command (Coincidence output 1) (RY10) is turned on while CH1 Present value (RWr10 to RWr11) and Point setting
(Coincidence output 1) (RWw0 to RWw1) match, Coincidence output 1 (RX10) and the coincidence output 1 terminal (EQU1) turn
off.
8)
If Reset command (Coincidence output 1) (RY10) is turned off while CH1 Present value (RWr10 to RWr11) and Point setting
(Coincidence output 1) (RWw0 to RWw1) match, Coincidence output 1 (RX10) and the coincidence output 1 terminal (EQU1) turn
on again.
9)
When CH1 Present value (RWr10 to RWr11) is more than Point setting (Coincidence output 1) (RWw0 to RWw1), the value in
Counter value greater (Coincidence output 1) (RWr0.b1) is 1.
10)
Turn on Reset command (Coincidence output 1) (RY10) to reset Coincidence output 1 (RX10) and the coincidence output 1
terminal (EQU1). If Coincidence output 1 (RX10) and the coincidence output 1 terminal (EQU1) remain on, the next coincidence
output cannot be detected.