230
(2) When the coincidence output function does not perform normal operation
(a) When Coincidence output 1 to 4 (RX10 to RX13) do not turn on
(b) When Coincidence output 1 to 4 (RX10 to RX13) does not turn off
*1
For
Δ
T
1
, refer to the following.
(c) When only Coincidence output 1 to 4 terminals (EQU1 to EQU4) do not turn on
Check item
Action
Are Coincidence output 1 to 4 assigned properly?
Review the setting in Coincidence output channel assignment
setting (address: 0101
H
).
Are the comparison conditions for Coincidence output 1 to 4
proper?
Review the setting in Coincidence output comparison condition
setting (address: 0102
H
).
Is Initial data setting request flag (RY9) or Setting change request
(Coincidence output 1 to 4) (RY14 to RY17) turned on after
changing Point setting (Coincidence output 1)/Lower limit value
setting (Coincidence output 1) (RWw0 to RWw1) to Upper limit
value setting (Coincidence output 4) (RWwE to RWwF)?
Turn on Initial data setting request flag (RY9) or Setting change
request (Coincidence output 1 to 4) (RY14 to RY17) after changing
Point setting (Coincidence output 1)/Lower limit value setting
(Coincidence output 1) (RWw0 to RWw1) to Upper limit value setting
(Coincidence output 4) (RWwE to RWwF).
Is Reset command (Coincidence output 1 to 4) (RY10 to RY13) off?
(Only when Coincidence output is selected as the comparison
condition)
Turn off Reset command (Coincidence output 1 to 4) (RY10 to
RY13).
Are the settings in Point setting (Coincidence output 1)/Lower limit
value setting (Coincidence output 1) (RWw0 to RWw1) to Upper
limit value setting (Coincidence output 4) (RWwE to RWwF) within
the count range of the ring counter when the counter format is the
ring counter?
Set Point setting (Coincidence output 1)/Lower limit value setting
(Coincidence output 1) (RWw0 to RWw1) to Upper limit value setting
(Coincidence output 4) (RWwE to RWwF) within the count range of
the ring counter.
Check item
Action
Is the ON time of Reset command (Coincidence output 1 to 4)
(RY10 to RY13)
Δ
T
1
*1
or longer? (Only when Coincidence output is
selected as the comparison condition)
Set the ON time of Reset command (Coincidence output 1 to 4)
(RY10 to RY13) to
Δ
T
1
*1
or longer. (
Check item
Action
Is CH
Coincidence output enable command (RY20, RY38) on?
Turn on CH
Coincidence output enable command (RY20, RY38).
Is the external wiring to Coincidence output 1 to 4 terminals (EQU1
to EQU4) correct?
Check the external wiring and correct errors.