285
APPENDICES
A
Appendix 4 Intern
al C
ontrol Cycle and R
espo
nse D
elay T
ime
(b) Processing time (Normal value): Master station (RWr)
←
Remote device station
(RWr)
The following shows the processing time required until a count value is read by the master station after the
count value is counted by the high-speed counter module.
(SM × 1) + (LS × n1) + Processing time of the high-speed counter module (
Δ
T
1
)
• SM: Scan time of the program in the master station
• LS: Link scan time
• n1: The value provided by rounding up the value after the decimal point of (SM
÷
LS)
(c) Processing time (Normal value): Master station (RX)
←
Remote device station (RX)
The following shows the processing time required until Coincidence output 1 (RX10) is transmitted to the
master station after the high-speed counter module receives Reset command (Coincidence output 1) (RY10).
(The processing time required for transmitting Reset command (Coincidence output 1) (RY10) to the high-
speed counter module is not included.)
(SM × 1) + (LS × n1) + Processing time of the high-speed counter module (
Δ
T
1
)
• SM: Scan time of the program in the master station
• LS: Link scan time
• n1: The value provided by rounding up the value after the decimal point of (SM
÷
LS)
(d) Processing time (Normal value): Master station (RWw)
→
Remote device station
(RWw)
The following shows the transmission time required for setting Point setting (Coincidence output 1) (RWw0 to
RWw1) to the high-speed counter module. (The processing time required for transmitting Setting change
request (Coincidence output 1) (RY14) to the high-speed counter module is not included.)
(SM × n2) + (LS × 1) + Processing time of the high-speed counter module (
Δ
T
1
)
• SM: Scan time of the program in the master station
• LS: Link scan time
• n2: The value provided by rounding up the value after the decimal point of (LS
÷
SM)