156
8.15
Pulse Measurement Function
The pulse measurement function measures the ON width or OFF width of pulses that are input to the external input
terminals, CH
Function input terminal (FUNC1, FUNC2) or CH
Latch counter input terminal (LATCH1, LATCH2).
When the next pulse is measured, the measured value is written over the previous value.
(1) Setting method of the pulse measurement function
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select a high-speed counter module in "List of stations"
[CC IE Field Configuration]
[Parameter Processing of Slave Station]
2.
Set "CH
Operation mode setting " to "3: Pulse Measurement Mode".
3.
Set the pulse width to be measured in "CH
Pulse measurement setting (Function input
terminal)".
4.
Set the pulse width to be measured in "CH
Pulse measurement setting (Latch counter input
terminal)".
Function input terminal
(FUNC1/FUNC2)
Pulses
High-speed
counter module
Remote register
CH Measured pulse value
(Function input terminal)
(RWr1C to RWr1D, RWr34 to RWr35)
Analysis
Latch counter input terminal
(LATCH1/LATCH2)
Pulses
Remote register
CH Measured pulse value
(Latch counter input terminal)
(RWr1E to RWr1F, RWr36 to RWr37)
Analysis
Summary of Contents for NZ2GFCF-D62PD2
Page 1: ......
Page 2: ......
Page 54: ...52 Memo ...
Page 206: ...204 Memo ...
Page 303: ......
Page 304: ......