213
CHAPTER 11 TROUBLESHOOTING
11
11.2 Er
ror
Code List
31
H
Moderate error
Upper limit
value setting
error
(Coincidence
output
)
The value in Upper limit
value setting (Coincidence
output
) is smaller than
the value in Lower limit
value setting (Coincidence
output
).
indicates the channel
where settings are
incorrect.
indicates the number of
Coincidence output on
which this error occurred.
If the
parameters are
written with the
parameter
processing of
the slave
station, or Initial
data processing
completion flag
(RY8) or Initial
data setting
request flag
(RY9) is turned
off then on:
*13
If Setting
change request
(Coincidence
output
) (RY14
to RY17) is
turned off then
on:
*6
If the
parameters are
written with the
parameter
processing of
the slave
station, or Initial
data processing
completion flag
(RY8) or Initial
data setting
request flag
(RY9) is turned
off then on:
*13
If Setting
change request
(Coincidence
output
) (RY14
to RY17) is
turned off then
on:
*3
Set the values that satisfy the
condition "Lower limit value
setting (Coincidence output
)
≤
Upper limit value setting
(Coincidence output
)", and
perform one of the following
operations.
• If Initial data processing
request flag (RX8) is on, turn
off then on Initial data
processing completion flag
(RY8).
• If the parameters are written
with the parameter
processing of the slave
station, or Initial data setting
completion flag (RX9) is on,
turn off then on Initial data
setting request flag (RY9).
• If Initial data processing
request flag (RX8) and Initial
data setting completion flag
(RX9) are off, turn off then on
Setting change request
(Coincidence output
)
(RY14 to RY17).
351
H
Moderate error
Cam switch
function,
number of steps
setting error
(Output 1)
A value other than 0 to 16
is set in Cam switch
function, number of steps
(Output 1) (address:
1501
H
).
indicates the channel
where settings are
incorrect.
*7 *3
Set Cam switch function,
number of steps (Output 1)
(address: 1501
H
) to a value
between 0 and 16, and turn off
then on CH
Cam switch
execute command (RY26,
RY3E).
..
.
..
.
..
.
..
.
..
.
..
.
..
.
359
H
Moderate error
Cam switch
function,
number of steps
setting error
(Output 9)
A value other than 0 to 16
is set in Cam switch
function, number of steps
(Output 9) (address:
1901
H
).
indicates the channel
where settings are
incorrect.
*7 *3
Set Cam switch function,
number of steps (Output 9)
(address: 1901
H
) to a value
between 0 and 16, and turn off
then on CH
Cam switch
execute command (RY26,
RY3E).
360
H
Moderate error
Cam switch
function,
number of steps
setting error
(Output 10)
A value other than 0 to 16
is set in Cam switch
function, number of steps
(Output 10) (address:
1981
H
).
indicates the channel
where settings are
incorrect.
*7 *3
Set Cam switch function,
number of steps (Output 10)
(address: 1981
H
) to a value
between 0 and 16, and turn off
then on CH
Cam switch
execute command (RY26,
RY3E).
..
.
..
.
..
.
..
.
..
.
..
.
..
.
366
H
Moderate error
Cam switch
function,
number of steps
setting error
(Output 16)
A value other than 0 to 16
is set in Cam switch
function, number of steps
(Output 16) (address:
1C81
H
).
indicates the channel
where settings are
incorrect.
*7 *3
Set Cam switch function,
number of steps (Output 16)
(address: 1C81
H
) to a value
between 0 and 16, and turn off
then on CH
Cam switch
execute command (RY26,
RY3E).
Error code
(hexadecimal)
Classification
Error name
Description and
cause
Operation of when an error
occurs
Action
Error CH
The other
CHs
Summary of Contents for NZ2GFCF-D62PD2
Page 1: ......
Page 2: ......
Page 54: ...52 Memo ...
Page 206: ...204 Memo ...
Page 303: ......