170
(a) Method for clearing a warning
*1
A warning results in the following state five seconds after the error cause is removed or CH
Error reset command
(RY36, RY4E) is turned off then on.
• Warning status flag (RX7) turns off.
• CH
Warning status (RX37, RX4F) of a channel where the error cause is removed turns off.
• CH
Latest warning code (RWr23, RWr3B) of a channel where the error cause is removed is cleared.
• The ERR. LED turns off.
Ex.
Operation to clear Station number switch change failure (error code: 0160
H
)
Error type
Clearing an error
Minor error
Warning
Error code:
Other than
050
H
A warning is cleared five seconds after the error cause is removed.
*1
Error code:
050
H
Turning off then on CH
Error reset command (RY36, RY4E) resets
the warning status of each channel.
*1
Station No.1
(normal)
Station No.1
(normal)
ON
ON
OFF
OFF
Warning status flag
(RX7)
Station number
setting switch
CH1 Latest warning code
(RWr23)
ERR. LED
Remote READY
(RXB)
OFF
Station No.10
(error)
OFF
0
Flashing
0
5 seconds
0160
H
(station number switch
change failure)
Controlled by the high-speed counter module