244
RX29
Update flag
(Latch count
value)
• This signal turns on when CH
Latch count value (RWr12 to RWr13, RWr2A to RWr2B) is
updated.
(
CH
Latch count value (RWr12 to RWr13, RWr2A to RWr2B) is updated without resetting
this flag.
• This signal turns off when CH
Update flag reset command (Latch count value) (RY28,
RY40) is turned on.
• Up to
Δ
T
1
*1
delay occurs until this signal turns on after CH
Latch count value (RWr12 to
RWr13, RWr2A to RWr2B) is updated.
(For the overview of the operation, refer to the description of CH
Update flag reset
completed (Latch count value) (RX28, RX40).)
*1
For
Δ
T
1
, refer to Page 283, Appendix 4.
CH1
Update flag
(Sampling count
value)
• This signal turns on when CH
Sampling count value (RWr12 to RWr13, RWr2A to RWr2B)
is updated.
(
• CH
Sampling count value (RWr12 to RWr13, RWr2A to RWr2B) is updated without
resetting this flag.
• This signal turns off when CH
Update flag reset command (Sampling count value) (RY28,
RY40) is turned on.
• Up to
Δ
T
1
*1
delay occurs until this signal turns on after CH
Sampling count value (RWr12
to RWr13, RWr2A to RWr2B) is updated.
(For the overview of the operation, refer to the description of CH
Update flag reset
completed (Sampling count value) (RX28, RX40).)
*1
For
Δ
T
1
, refer to Page 283, Appendix 4.
RX41
CH2
Update flag
(Periodic pulse
count value)
• This signal turns on when CH
Periodic pulse count, difference value (RWr12 to RWr13,
RWr2A to RWr2B), CH
Periodic pulse count, present value (RWr14 to RWr15, RWr2C to
RWr2D), and CH
Periodic pulse count value update check (RWr16 to RWr17, RWr2E to
RWr2F) are updated.
(
• CH
Periodic pulse count, difference value (RWr12 to RWr13, RWr2A to RWr2B), CH
Periodic pulse count, present value (RWr14 to RWr15, RWr2C to RWr2D), and CH
Periodic pulse count value update check (RWr16 to RWr17, RWr2E to RWr2F) are updated
without resetting this flag.
• This signal turns off when CH
Update flag reset command (Periodic pulse count value)
(RY28, RY40) is turned on.
• Up to
Δ
T
1
*1
delay occurs until this signal turns on after CH
Periodic pulse count, difference
value (RWr12 to RWr13, RWr2A to RWr2B), CH
Periodic pulse count, present value
(RWr14 to RWr15, RWr2C to RWr2D), and CH
Periodic pulse count value update check
(RWr16 to RWr17, RWr2E to RWr2F) are updated.
(For the overview of the operation, refer to the description of CH
Update flag reset
completed (Periodic pulse count value) (RX28, RX40).)
*1
For
Δ
T
1
, refer to Page 283, Appendix 4.
Remote input