248
RX36
CH1
Error status
• This signal turns on when a moderate error or major error occurs on a channel
corresponding to this signal.
• This signal turns off when CH
Error reset command (RY36, RY4E) is turned on and no
moderate error or major error newly occurs.
*1
This signal cannot be reset arbitrarily by output signals such as CH
Error reset command (RY36, RY4E) depending on warning codes (error
codes of minor errors). For details, refer to Page 208, Section 11.2.
RX4E
CH2
RX37
CH1
Warning status
• This signal turns on when a minor error occurs on a channel corresponding to this signal.
• This signal turns off when CH
Error reset command (RY36, RY4E) is turned on and no
minor error newly occurs. Some warning codes (error codes of minor errors) cannot be reset
by turning on CH
Error reset command (RY36, RY4E). For details, refer to Page 208,
• This signal turns off when no minor error newly occurs five seconds after a minor error
occurred. (For the overview of the operation, refer to the description of CH
Error status
(RX36, RX4E).) However, this signal may not turn off even after five seconds depending on
warning codes (error codes of minor errors). For details, refer to Page 208, Section 11.2.
RX4F
CH2
Remote input
(RX) No.
Signal name
Description
Controlled by the high-speed counter module
Controlled by the program
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
CH Error reset command
(RY36, RY4E)
CH Latest error code
(RWr22, RWr3A)
CH Error status
(RX36, RX4E)
Error status flag
(RXA)
CH Latest warning code
(RWr23, RWr3B)
CH Warning status
(RX37, RX4F)
Warning status flag
(RX7)
1200
H
0
0
1050
H
*1
0
0
Summary of Contents for NZ2GFCF-D62PD2
Page 1: ......
Page 2: ......
Page 54: ...52 Memo ...
Page 206: ...204 Memo ...
Page 303: ......
Page 304: ......