46
(a) Monitoring area of the extension module
The remote buffer memory differs depending on the model of the extension module.
• Extension input module (NZ2EX2B1-16D)
*1
This is the value for when the module power supply is turned off then on or at the remote reset.
*2
This shows whether read or write from programs is possible.
R: Readable
W: Writable
• Extension output module (NZ2EX2B1-16T)
*1
This is the value for when the module power supply is turned off then on or at the remote reset.
*2
This shows whether read or write from programs is possible.
R: Readable
W: Writable
Number of ON times integration value Y0 to Number of ON times integration value YF are written to a nonvolatile memory in
the specified cycle.
Address
Description
Default
*1
Read/
Write
*2
Decimal
Hexadecimal
1792
0700
H
Extension module identification code
0000
H
R
1793 to 2047
0701
H
to 07FF
H
System area
⎯
⎯
Address
Description
Default
*1
Read/
Write
*2
Decimal
Hexadecimal
1792
0700
H
Extension module identification code
0000
H
R
1793 to 1807
0701
H
to 070F
H
System area
⎯
⎯
1808 to 1809
0710
H
to 0711
H
Number of ON times integration
value
Y0
0
R
1810 to 1811
0712
H
to 0713
H
Y1
0
R
1812 to 1813
0714
H
to 0715
H
Y2
0
R
1814 to 1815
0716
H
to 0717
H
Y3
0
R
1816 to 1817
0718
H
to 0719
H
Y4
0
R
1818 to 1819
071A
H
to 071B
H
Y5
0
R
1820 to 1821
071C
H
to 071D
H
Y6
0
R
1822 to 1823
071E
H
to 071F
H
Y7
0
R
1824 to 1825
0720
H
to 0721
H
Y8
0
R
1826 to 1827
0722
H
to 0723
H
Y9
0
R
1828 to 1829
0724
H
to 0725
H
YA
0
R
1830 to 1831
0726
H
to 0727
H
YB
0
R
1832 to 1833
0728
H
to 0729
H
YC
0
R
1834 to 1835
072A
H
to 072B
H
YD
0
R
1836 to 1837
072C
H
to 072D
H
YE
0
R
1838 to 1839
072E
H
to 072F
H
YF
0
R
1840 to 2047
0730
H
to 07FF
H
System area
⎯
⎯
Summary of Contents for NZ2GFCF-D62PD2