238
RX9
Initial data setting
completion flag
• This signal is used as an interlock for turning on/off Initial data setting request flag (RY9)
when the setting values in the parameter area of the remote buffer memory are changed or
the setting values of the extended parameter area are saved into the nonvolatile memory.
• While this signal is on, the high-speed counter module does not count pulses.
This signal turns off in the following cases.
• Until Initial data setting request flag (RY9) is turned on after the module is powered on
• Initial data setting request flag (RY9) is turned off when the setting values in the parameter
area of the remote buffer memory are normal.
This signal turns on in the following case.
• When Initial data setting request flag (RY9) is turned on
• After checking that the initial data setting processing is completed (this signal turns off) and
Initial data processing request flag (RX8) turns off, turn on CH
Count enable command
(RY24, RY3C) to start pulse counting.
• Remote output signals other than CH
Error reset command (RY36, RY4E) that are already
turned on when this signal turns off are recognized as they are turned on right after this
signal turns off.
• When Initial data processing request flag (RX8) is off and at the rising state of either of
Coincidence output 1 or Coincidence output 2 for which the preset/replace (at coincidence
output) function is enabled from the comparison result at when this signal turns off, the count
value is replaced with the preset value. (However, this operation is performed only when
Comparison output setting (address: 0100
H
) is set to Coincidence Output Function (0) and
CH
Operation mode setting (address: 0120
H
, 0140
H
) is set to Normal Mode (0).)
• If an error occurs, such as when a value out of the setting range of the remote register
(RWw) or the remote buffer memory is detected, this signal does not turn off even if Initial
data setting request flag (RY9) is turned off. (This signal remains on.) In this case, remove
the error cause and turn on then off Initial data setting request flag (RY9). In addition, the
OFF time must be longer than
Δ
T
1
*1
.
*1
For
Δ
T
1
, refer to Page 283, Appendix 4.
Remote input
(RX) No.
Signal name
Description
Controlled by the high-speed counter module
Controlled by the program
Remote READY
(RXB)
Initial data setting completion flag
(RX9)
Initial data setting request flag
(RY9)
Parameter area
(Setting value A)
The operation is
performed with
the setting value A.
The operation is
performed with
the setting value B.
The setting value is
changed by the user.
(Setting value B)
ON
OFF
ON
ON
ON
OFF
OFF
Summary of Contents for NZ2GFCF-D62PD2
Page 1: ......
Page 2: ......
Page 54: ...52 Memo ...
Page 206: ...204 Memo ...
Page 303: ......
Page 304: ......