5. HOW TO USE THE PROGRAM
5 - 29
(l) Torque limit value switching (TLP/TLN/TQL)
Using the maximum torque as 100.0%, limit the generated torque of the servo motor.
1) Program example
Command Description
SPN (1500)
STA (100)
STB (200)
MOV (1000)
Servo motor speed
Acceleration time constant
Deceleration time constant
Absolute value travel command
1500 [r/min]
100 [ms]
1: 200 [ms]
10
STM
μ
m
SYNC (1)
Suspend the step until PI1 (Program input 1) is switched on.
a)
TLP (800)
Forward rotation torque limit
800 [0.1%]
b)
SYNC (2)
Suspend the step until PI2 (Program input 2) is switched on.
c)
TLN (500)
TIM (100)
MOV (500)
Reverse rotation torque limit
Dwell
Absolute value travel command
500 [0.1%]
100 [ms]
1000 [×10
STM
μ
m]
d)
e)
SYNC (3)
Suspend the step until PI3 (Program input 3) is switched on.
f)
TQL (300)
STOP
Torque limit
Program stop
300 [0.1%]
g)
h)
[Pr. PA11] setting
[Pr. PA11] setting
h) Program stop
g) Torque limit
g) Torque limit The torque limit value returns
to the parameter setting value
by program stop.
d) Reverse rotation
torque limit
b) Forward rotation torque limit
Forward rotation torque limit
Reverse rotation torque limit
PI1 (Program input 1)
PI2 (Program input 2)
PI3 (Program input 3)
Servo motor
speed
a) PI1-on
f) PI3-on
c) PI2-on
80.0%
30.0%
e) 100 ms
[Pr. PA12] setting
ON
OFF
ON
OFF
ON
OFF
[Pr. PA12] setting
50.0%
30.0%
Reverse rotation
0 r/min
Forward rotation
Summary of Contents for MR-JE-100A
Page 49: ...2 SIGNALS AND WIRING 2 28 MEMO...
Page 73: ...3 DISPLAY AND OPERATION SECTIONS 3 24 MEMO...
Page 213: ...5 HOW TO USE THE PROGRAM 5 68 MEMO...
Page 275: ...6 APPLICATION OF FUNCTIONS 6 62 MEMO...
Page 355: ...8 TROUBLESHOOTING 8 8 MEMO...
Page 359: ...9 OPTIONS AND PERIPHERAL EQUIPMENT 9 4 MEMO...
Page 391: ...10 COMMUNICATION FUNCTION MITSUBISHI ELECTRIC GENERAL PURPOSE AC SERVO PROTOCOL 10 32 MEMO...