Power Network Application Trainer
– Earth / Ground network impedance analysing
148
8. Use same test probe setup for MI 3295M as in previous case
Example of result with FAIL indication:
In case of FAIL result on real field measurements it is obligatory to investigate and
improve the earthing of the tested object.
4.3 GPR Measurement exercises
Instrument used:
MI 3290 Earth Analyser
MI 3295S Step Contact Voltage Measuring System
MI 3295M
Ground potential rise is carried out for properly design of electrical substations because
the high potential may be a hazard to people or equipment. Measurements are
performed:
circular around the tested object to measure equipotential lines (determination of
line strips, circular earthing loops….)
in straight line from the tested object to measure the gradient (step) voltage
Presented exercise will train you, how to perform GPR measurements by using:
MI 3290 instrument - used as current generator and volt-meter,
MI 3290 used as current generator and MI 3295M as volt-meter,
MI 3295S used as current generator and MI 3295M as volt meter.