Power Network Application Trainer
– Insulation Analysis
217
8.2 Insulation resistance measurement on the transformer
–
regular condition
Note: Maximum applied test voltage to the tested transformer is 1kV!
Do not apply higher test voltage!
Exercise 1.1: Insulation resistance test (Spot test)
between primary and secondary
side of transformer
Figure 121-3: Transformer insulation resistance measurement setup (primary
– secondary side)
Method used
Simulated condition
Expected result
R
ISO
=17,5 GΩ
R
ISO
=18,1 GΩ
Table 75-3: Transformer insulation resistance test setup/result presentation (primary
– secondary side)
Measuring procedure
1. Under
MAIM MENU
MEASUREMENTS
menu select
Insulation Resistance
Test
measurement function