Power Network Application Trainer
– Insulation Analysis
223
Exercise 3.1: Insulation resistance test (Spot test)
between secondary side of
transformer and “pe” terminal (representing transformer housing)
Figure 123-3: Transformer Insulation resistance test setup (secondary side
– pe terminal)
Method used
Simulated condition
Expected result
R
ISO
= 7.29
GΩ
R
ISO
= 7.30
GΩ
Table 77-3: Transformer insulation resistance test setup/result presentation (secondary side
– pe
terminal)
Measuring procedure
1. Measurement and parameter setup is the same as it is presented in Exercise 1.1
2. Connect the test leads to the instrument and to the test object.
- Connect the red test probe (
+Rx
) to the secondary side of transformer
on the MI 3298 T training module (X terminal
– u or v orw)
- Connect the black test probe (
-Rx
) to the
“pe” terminal of the
transformer on the MI 3298 T training module
- Connect GUARD terminal to the secondary side of transformer on the
MI 3298 T training module (H terminals
– U or V or W)