Power Network Application Trainer
– Power generator, transformer, coils
183
There is FAIL indication and additional warning, that there was problem during
measurements.
Comparing results with the reference data on the transformer nominal plate, following
problem was detected:
a.
problem on windings C
: turn ratio was not calculated, so this is direct
point to open circuit (broken connection). We also propose, to perform
additional
winding
resistance
measurement
in
such
case.