Power Network Application Trainer
– Earthing / Grounding network impedance measurement
84
4.1.1.1.2
4 Pole measuring method
Figure 61-2: 4-pole earth resistance measurement with MI 3290
4-pole method uses four-wire connection, so the resistance of test cables is excluded
from the measurement result. It is possible to select the measurement frequency
selection from 55 Hz to 15 kHz (fixed / sweep mode). In this exercise fixed frequency
measurement is used (329 Hz) in first step and frequency sweep in the second one.
Switch position Simulated condition
Application
Expected result
Regular measurement place
condition (simulated resistive earth
character), single and sweep
frequency measurement
Industrial areas
Transformer stations
Radio towers
Pylons without ground wire
connection
Solar power plants
Wind &water turbine
Ze = 2.55
Ω @ 329 Hz, single mode
Ze = 2.55
Ω @ sweep mode (329 Hz)
Table 15-2: Measurement setup/result for 3-pole measurement method
Measuring procedure
– single frequency measurement:
1. Select proper switch position on the training module.
2. Under
Earth
test function select the
4P
measurement method
Summary of Contents for MI 3298
Page 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Page 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Page 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Page 228: ...MI 3290 Earth Analyser 228 ...
Page 229: ...MI 3280 Digital Transformer Analyser 229 ...
Page 230: ...MI 3280 Digital Transformer Analyser 230 ...
Page 231: ...MI 3250 MicroOhm 10A 231 ...
Page 232: ...MI 3205 TeraOhmXA 5kV 232 ...