Power Network Application Trainer
– Earthing / Grounding network impedance measurement
102
earth connection on two foots. Total resistance (calculated from the partial results) is
still “inside” acceptable range, but separate foot resistance measurement shows that
two foots have broken connection what is extreme critical situation in real environment.
Switch position Simulated condition
Application
Expected result
Simulated broken foot Nm. 2 & 3
connection (simulated resistive
earth character), flex
measurement /
MI 3290
Pylons (mono and multi-leg)
with and without protective earth
cable connection
Ski lifts
Radio towers
Foot Nm. 1 approx.17,8
Ω
Foot Nm. 2 approx.391
Ω
Foot Nm. 3 approx.283
Ω
Foot Nm. 4 approx. 5,33
Ω
Z
tot calc
= 3,99
Ω
Table 25-2: S-Flex measurement setup/result presentation
From the “Expected results” column it is visible, that total foot earth impedance is in
expected range, but foot Nm. 2 & 3 are total out of scope. S
– Flex method is suitable
measurement method for analysing the selective foot conditions.
Measuring procedure
1. Repeat the connection setup and MI 3290 setting procedure as it is presented under
4.1.3.1 exercise. Select proper switch position on the training module.
Expected result for foot number 1:
Generated current is quite low due to high current probe resistance.
Since limit value was not set, there is no PASS/FAIL indication. Use the proper limit
value if you need to evaluate the result.
Since this measurement gives result only for the single foot, measurement needs to be
repeated also on the other foots.
Move the clamp to the next foot (sequential to foot 2, 3 and 4) and repeat the
measurement.
Expected result for foot number 2:
Expected result for foot number 3:
Summary of Contents for MI 3298
Page 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Page 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Page 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Page 228: ...MI 3290 Earth Analyser 228 ...
Page 229: ...MI 3280 Digital Transformer Analyser 229 ...
Page 230: ...MI 3280 Digital Transformer Analyser 230 ...
Page 231: ...MI 3250 MicroOhm 10A 231 ...
Page 232: ...MI 3205 TeraOhmXA 5kV 232 ...