![METREL MI 3298 Instruction Manual With Exercises Download Page 135](http://html1.mh-extra.com/html/metrel/mi-3298/mi-3298_instruction-manual-with-exercises_1778927135.webp)
Power Network Application Trainer
– Earthing / Grounding network impedance measurement
135
4.2 Step& Contact Voltage Measurement exercises
Instrument used:
MI 3290 Earth Analyser
MI 3295S Step Contact Voltage Measuring System
MI 3295M
For the presented exercises small step voltage probes is used for simulation and also
smaller distance, due to the training module dimensions.
4.2.1 Step voltage measurement with Earth Analyser MI 3290
Instrument used for current generation: MI 3290
Instrument used for step voltage measurement: MI 3295M
Note:
MI3290 could generate maximal current of 230 mA, so it is intended for
measurement of smaller objects. In these exercises, MI 3290 is used only as
current generator.
MI3295M is used in this application as Volt-meter with selected internal
resistance
of 1 kΩ (simulation of human body resistance).
Simulated conditions do not present same situation as it is in the real field.
MI 3295M meter re-calculates measured Step voltage to the real Step voltage
which could appears in case of fault/lightening condition. Generated current and
expected fault current should be entered as parameter into the parameter list of
MI 3295M meter.
Switch position
Simulated
condition
Applications
Expected result
MI3295M
Industrial areas
Transformer stations
Radio towers
Pylons with/without
protective earth cable
connection
Solar power plants
Wind & water turbine
Related to the position of
test probes.
Table 47-2: Step voltage measuring method setup/result presentation
Summary of Contents for MI 3298
Page 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Page 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Page 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Page 228: ...MI 3290 Earth Analyser 228 ...
Page 229: ...MI 3280 Digital Transformer Analyser 229 ...
Page 230: ...MI 3280 Digital Transformer Analyser 230 ...
Page 231: ...MI 3250 MicroOhm 10A 231 ...
Page 232: ...MI 3205 TeraOhmXA 5kV 232 ...