Power Network Application Trainer
– Earthing / Grounding network impedance measurement
117
4.1.5 HF measuring method
– resistance/inductive type with
simulated GW connection
Figure 75-2: HF measuring method setup
The HF measuring method is intended for earth resistance measurement of pylons
connected via overhead ground wire. The HF method automatically eliminates the
inductive component.
Switch position Simulated condition
Application
Expected result
Regular measurement place
condition (simulated resistance
/inductive earth character),
simulated ground wire connection
Pylons (mono and multi-leg)
with and without protective earth
cable connection
Ski lifts
Radio towers
Re = 2,7
Ω @ HF at 25 kHz, R type
Re = 6.2
Ω @ HF at 25 kHz, L type
Table 38-2: HF measurement method setup/result presentation
Measuring procedure:
6. Select proper switch position on the training module:
7. Under
Earth
test function select the
HF
measurement method
Summary of Contents for MI 3298