Power Network Application Trainer
– Earthing / Grounding network impedance measurement
125
4.1.6.2 Auto Sequence procedure - 4-Pole/ HF measuring method / S-
Flex
– broken earth connection with simulated GW connection
Figure 79-2:
4-pole, HF and S-Flex measurement setup
Switch position Simulated condition
Application
Expected result
Simulated broken foot Nm. 2 & 3
connection (simulated inductive
earth character), simulated ground
wire connection
Pylons (mono and multi-leg)
with and without protective earth
cable connection
Ski lifts
Radio towers
4-pole:
Ze = 1,78
Ω @ 329 Hz
HF:
Re = 6,7
Ω @ 25kHz
S-Flex:
Foot Nm. 1 approx. 14,76 Ω @ 329 Hz
Foot Nm. 2 approx. 348 Ω @ 329 Hz
Foot Nm. 3 approx. 1,767 kΩ@ 329 Hz
Foot Nm. 4 approx. 6,62 Ω @ 329 Hz
Z
tot calc
= 4,49
Ω
Table 41-2: 4-pole, HF and S-Flex setup/result presentation
Three measurement methods (4-pole, HF
– 25 kHz and S-Flex method) executed under
single Auto Sequence will be used under same test object for comparing the results and
executed with single press on “Start” button.
To join three measuring methods under single Auto Sequence, we need to prepare
appropriate one and connect the measured object properly, to be ready for all selected
measurement methods.
Summary of Contents for MI 3298
Page 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Page 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Page 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Page 228: ...MI 3290 Earth Analyser 228 ...
Page 229: ...MI 3280 Digital Transformer Analyser 229 ...
Page 230: ...MI 3280 Digital Transformer Analyser 230 ...
Page 231: ...MI 3250 MicroOhm 10A 231 ...
Page 232: ...MI 3205 TeraOhmXA 5kV 232 ...